Accident Summary Nr: 14371678 - EXPOSURE TO CHLORINE GAS

Accident Summary Nr: 14371678 -- Report ID: 0522000 -- Event Date: 01/18/1985
Inspection NrDate OpenedSICNAICSEstablishment Name
248461601/21/198520860Coca Cola Bottling Of Cincinnati

Abstract: THIS EVENT OCCURRED AT A SOFT DRINK BOTTLING PLANT. EMPLOYEE #1 WAS IN THE PROCESS OF DISCONNECTING A COMPRESSED GAS CYLINDER CONTAINING CHLORINE FROM A MODEL #91-100 WALLACE AND TIERNAN GAS CHLORINATION UNIT. THE EMPLOYEE THOUGHT THAT HE HAD TURNED THE TOP VALVE HANDLE ON THE SUPPOSEDLY EMPTY COMPRESSED GAS CYLINDER TO THE CLOSED POSITION, BUT CHLORINE GAS CAME HISSING OUT OF THE CYLINDER WHEN HE DISCONNECTED THE AUTOMATIC CHANGE-OVER UNIT FROM THE CYLINDER. EMPLOYEE #3 HAPPENED TO BE WORKING ON A LADDER NEAR THE CHLORINE ROOM WHEN THE LEAK OCCURRED. EMPLOYEE #2 APPROACHED THE CHLORINE ROOM IN ORDER TO EVALUATE AND ASSESS THE SITUATION. THE INJURED EMPLOYEES EXPERIENCED BURNING, TEARING EYES AND BURNING, IRRITATED RESPIRATORY TRACTS, ALONG WITH COUGHING AND DIFFICULTY TAKING DEEP BREATHS. CONTRIBUTING FACTORS INCLUDED: A CYLINDER VALVE THAT WAS DIFFICULT TO COMPLETELY CLOSE; A MALFUNCTIONING "EMPTY" INDICATOR; A LACK OF SCALES AND A LACK OF LEAK CHECKS.

Keywords: BURN, EYE, RESPIRATORY, COMPRESSED GAS, CHLORINE, VALVE, RESPIRATOR

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 2484616 Hospitalized injury Poisoning(Systemic) Occupation not reported
2 2484616 Hospitalized injury Poisoning(Systemic) Occupation not reported
3 2484616 Hospitalized injury Poisoning(Systemic) Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close