Accident Summary Nr: 14354096 - ELECTRIC SHOCK - GROUND FAULT IN RELAY

Accident Summary Nr: 14354096 -- Report ID: 0419700 -- Event Date: 10/05/1990
Inspection NrDate OpenedSICNAICSEstablishment Name
1834645210/10/199076990Neel Mechanical

Abstract: AN EMPLOYEE WAS REMOVING INSULATION FROM A COOLING PIPE ATTACHED TO A HEATING AND AIR CONDITIONING UNIT. HE WAS DOING THIS SO HE COULD CLEAN THE COLD WATER VALVE. HE WAS HOLDING ONTO A SPRINKLER PIPE AT THE TIME. THE EMPLOYEE ACCIDENTALLY CUT INTO A 24-VOLT-DC CONDUCTOR. THIS CONDUCTOR WAS ACTUALLY ENERGIZED AT 277 VOLTS AC BECAUSE OF A FRAYED CONDUCTOR AT THE RELAY. THE FRAYED CONDUCTOR WAS CONTACTING THE 24-VOLT-DC RELAY TERMINAL. (THE CONTROLS INVOLVED WERE MANUFACTURED BY STAEFA, INC.) THE EMPLOYEE WAS ELECTROCUTED.

Keywords: ELECTRICAL, E GI VII, ELECTROCUTED, GROUND FAULT, ELECTRIC CONDUCTOR, SYSTEM GROUNDING

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 18346452 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.