Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 14340392 - ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC EQUIPMENT

Accident Summary Nr: 14340392 -- Report ID: 0418400 -- Event Date: 08/17/1987
Inspection NrDate OpenedSICNAICSEstablishment Name
10186026008/18/198730890T M Poly-Film, Inc.

Abstract: AN EMPLOYEE WAS PASSING BETWEEN A PLASTIC SHEET WINDING MACHINE AND A BUILDING COLUMN. THE 120-VOLT WINDING MACHINE HAD A GROUND FAULT AND AN OPEN GROUNDING CONDUCTOR. THE STEEL COLUMN HAD GROUNDED ELECTRIC EQUIPMENT MOUNTED ON ITS SURFACE. THE EMPLOYEE, WHO WAS SWEATING, WAS ELECTROCUTED WHEN HE CONTACTED THE MACHINE AND THE COLUMN AT THE SAME TIME. ANOTHER EMPLOYEE PERFORMED CPR ON THE INJURED EMPLOYEE. WHEN THAT DID NOT REVIVE HIM, TWO OTHER EMPLOYEES ATTEMPTED TO MOVE THE INJURED EMPLOYEE. THEY LIFTED HIM; AND, WHEN THEY CONTACTED THE WINDING MACHINE, THEY RECEIVED ELECTRIC SHOCKS. VARIOUS EMPLOYEES HAD COMPLAINED OF RECEIVING ELECTRIC SHOCKS FROM THE MACHINE FOR AT LEAST 3 WEEKS BEFORE THE ACCIDENT.

Keywords: ELECTRICAL, CPR, E GI VII, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, ELEC EQUIPMENT--MISC

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 101860260 Fatality Electric Shock Supervisors, production occupations
2 101860260 Non Hospitalized injury Electric Shock Occupation not reported
3 101860260 Non Hospitalized injury Electric Shock Misc. metal & plastic processing machine operators

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.