Accident Summary Nr: 14304646 - EMPLOYEE INHALED HIGH CONCENTRATION OF CHLORINE

Accident Summary Nr: 14304646 -- Report ID: 1050210 -- Event Date: 10/10/1986
Inspection NrDate OpenedSICNAICSEstablishment Name
254022711/18/198649410Seward, City Of

Abstract: AT ABOUT 9:30 PM ON OCTOBER 10, 1986, A WATER TREATMENT OPERATOR (EMPLOYEE #1) OPENED THE DOOR TO A CHLORINATOR ROOM DURING FLOOD CONDITIONS. AN ELECTRICAL SHORT CIRCUIT CAUSED THE CHLORINATOR TO CONTINUE RUNNING AFTER THE WATER FLOW HAD STOPPED. THE HIGH CONCENTRATION OF CHLORINE IN THE TREATMENT CIRCUIT LINE CORRODED A COPPER PIPE IN THE CHLORINATOR ROOM. THIS RESULTED IN WATER WITH A HIGHER THAN USUAL CONCENTRATION OF CHLORINE BEING SPRAYED AROUND THE ROOM FROM HOLES IN THE PIPELINE. EMPLOYEE #1 THEREFORE INHALED A HIGHER CONCENTRATION OF CHLORINE THAN HE HAD EXPECTED. A CHLORINE FULL-FACE RESPIRATOR, LOCATED IN AN ADJACENT ROOM, WAS NOT USED. THE CHLORINE MONITOR IN THE CHLORINATOR ROOM EVENTUALLY FUNCTIONED BY TURNING A VENTILATION FAN ON. HOWEVER, THE AIR EXCHANGE RATE WAS NOT SUFFICIENT TO PREVENT THE BUILD UP OF CHLORINE GAS.

Keywords: RESPIRATORY, INHALATION, CHLORINE, CHLORINE ROOM, PIPE, TOXIC FUMES, RESPIRATOR

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 2540227 Hospitalized injury Other Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close