Accident Summary Nr: 14292320 - ELECTRIC SHOCK - GROUND FAULT IN ATTACHMENT PLUG FOR WELDER

Accident Summary Nr: 14292320 -- Report ID: 0355110 -- Event Date: 01/26/1988
Inspection NrDate OpenedSICNAICSEstablishment Name
10568258701/26/198833650Metal Castings, Div. Of Line Power Mfg. Corp.

Abstract: AN EMPLOYEE WAS ELECTROCUTED WHILE USING A 480-VOLT WELDER. UPON INVESTIGATION, THE TWIST-LOCK ATTACHMENT PLUG FOR THE WELDER WAS FOUND TO HAVE ITS EQUIPMENT GROUNDING CONDUCTOR (GREEN) CONNECTED TO ONE OF THE PHASE TERMINALS. THIS GROUND FAULT ENERGIZED THE FRAME OF THE WELDER AT 277 VOLTS.

Keywords: ELECTRICAL, E GI VII, ELECTROCUTED, WELDER, ATTACHMENT PLUG, GROUND FAULT, EQUIPMENT GROUNDING

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 105682587 Fatality Electric Shock Miscellaneous hand working occupations

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.