Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 14194328 - ELECTRIC SHOCK - CONTACT WITH UNDERGROUND LINE

Accident Summary Nr: 14194328 -- Report ID: 0352440 -- Event Date: 07/10/1985
Inspection NrDate OpenedSICNAICSEstablishment Name
284011407/16/198516230Ferguson Trenching Company

Abstract: AN EMPLOYEE WAS TO SPLICE A 13-KILOVOLT UNDERGROUND POWER CABLE IN A PIT THAT WAS 3 FEET DEEP, 54 INCHES WIDE, AND 5 FEET LONG. THE CABLE WAS PRESUMED TO BE DEENERGIZED AS IT HAD NOT BEEN CONNECTED TO ITS POWER SOURCE. HOWEVER, THE OTHER END OF THE CABLE WAS CONNECTED TO A TRANSFORMER AT THE REAR OF A FAST-FOOD RESTAURANT THAT WAS UNDER CONSTRUCTION ABOUT 60 FEET FROM THE PIT. THE SECONDARY OF THE TRANSFORMER WAS CONNECTED TO A PANELBOARD AT THE RESTAURANT. AN ELECTRICIAN INSTALLING THE ELECTRICAL SERVICE IN THE RESTAURANT HAD CONNECTED A FLEXIBLE CORD FROM THE 240-VOLT TEMPORARY SERVICE AT THE SITE TO THE PANELBOARD. CURRENT FROM THE TEMPORARY SERVICE BACKFED THE TRANSFORMER, ENERGIZING THE CABLE ON WHICH THE EMPLOYEE WAS WORKING. WHEN THE EMPLOYEE CONTACTED THE CABLE, HE RECEIVED AN ELECTRIC SHOCK FOR WHICH HE WAS HOSPITALIZED. HE HAD NOT TESTED THE CABLE BEFORE HE STARTED WORK.

Keywords: VOLTAGE BACKFEED, ELECTRICAL, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, UNDRGRD POWER LINE

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 2840114 Hospitalized injury Electric Shock Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close