Accident Summary Nr: 132540.015 - Employee is burned by arc flash

Accident Summary Nr: 132540.015 -- Report ID: 0418200 -- Event Date: 10/05/2020
Inspection NrDate OpenedSICNAICSEstablishment Name
1497392.01510/14/2020221122Georgia Power Company

Abstract: At 3:30 p.m. on October 5, 2020, an employee (crew leader) and his 5 crew members were assigned to repair an underground cable that was damaged by construction site activities. An excavator was brought in to gain access to the damaged underground cable, which was de-energized prior to conducting the repairs. After that job was completed, the crew was instructed to repair a second cable, which was previously faulted in the same area. An impulse generator was utilized to locate the cable's fault, which was determined to be located near the same ditch that was open for the prior repair. Once the general location was determined, the impulse generator was removed, the cable was isolated and grounded at both ends. Also, the cable was tested for the absence of voltage. The crew hand dug the ditch using shovels. The crew identified the already isolated cable and tested for the absence of voltage. The faulted cable, alongside two other cables, was buried underneath three other underground electric cables. The employee (crew leader) got into the ditch to positively identify the faulted cable visually. He was moving the cable on top of the faulted cable with his insulated boot to visually see the fault on the suspected faulty cable. When he moved the energized cable, it failed and caused a flash that burned his right dielectric boot and forearm. The employee suffered third degree burns on his right forearm and hand since the skin was exposed. The employee stated that he rolled his (arc-rated protective shirt) sleeves up, because he was hot after working all day long. Also, the suspected faulty cable was out of reach and did not present an electrical hazard. The employee was hospitalized.

Keywords: Burn, Cable, Ditch, Electric Arc Flash, Electric Cable, Excavator, Forearm, Hand, High Voltage, Protective Clothing, Repair
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Powerline, transmission line Maintenance or repair  

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation Construction
1 1497392.015 38 M Hospitalized injury Electrical power installers and repairers Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Temporary work (buildings, facilities)
Fatality Cause:

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.