Accident Summary Nr: 128268.015 - One employee is killed, two are injured in 4-kV arc flash in

Accident Summary Nr: 128268.015 -- Report ID: 0522500 -- Event Date: 08/03/2020
Inspection NrDate OpenedSICNAICSEstablishment Name
1486468.01508/04/2020221112Ohio Valley Electric Corporation

Abstract: At 8:41 a.m. on August 3, 2020, two employees were working as electricians for an electric power utility. They and Employee #3 were working at a coal-fired generating station. The two electricians, Employees #1 and #2, were troubleshooting the generating station's pulverizer and pulverizer fan number 6 breaker. The breaker would not rack out from an energized 4,000-volt buss. The two electricians opened up the breaker cabinet door to access the breaker and to visually inspect the racking mechanism. The two employees unbolted and removed the front interphase barrier cover. Employee #1 started to unbolt the horizontal steel barrier plate directly below the exposed primary side of the breaker in order to view the back portion of the lower racking mechanism. As he was doing this, an arc flash occurred. Employee #1 received arc flash burns to his upper body. Employee #2, located behind Employee #1, also received burns. Employee #3, who responded to the incident, received an injury to his leg. Employees #1 and #2 were hospitalized with serious burn injuries. Employee #1 died on August 26, 2020, as a result of the injuries he had received. Employee #2 was hospitalized with serious burns. Employee #3 was treated for a contusion to his left leg.

Keywords: Burn, Circuit Breaker, Contusion, E PTD (power generation), Elec Utility Work, Electric Arc, Electrical, Electrical Cabinet, Electrical Fault, Electrician, Energized, Leg, Lockout, PPE, Torso

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 1486468.015 58 M Fatality Electricians
2 1486468.015 57 M Hospitalized injury Electricians
3 1486468.015 1 M Non Hospitalized injury Supervisors; electricians & power transm. install.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.