Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 121713.015 - Employees working on transformer are burned by arc flash

Accident Summary Nr: 121713.015 -- Report ID: 0419400 -- Event Date: 11/14/2019
Inspection NrDate OpenedSICNAICSEstablishment Name
1445072.01511/15/2019221122Entergy Mississippi, Llc

Abstract: At 8:00 a.m. on November 14, 2019, three employees were working for an integrated electric power utility. It produced and distributed electricity. The employees installed and repaired electric power equipment. The employees had been working for twenty-four hours. They were fifteen minutes into the twenty-fifth hour when the incident occurred. The three employees were phasing (verifying the voltage of) a run of 480-volt cables and a transformer that they had installed in a below ground electrical vault to replace existing equipment. The leads for the multimeter were too short to reach the contact points of the three phase conductors that were to be tested. The employees improvised by utilizing a spare cable to bridge the gap. The lead journeyman cable splicer and Employee #1 held the cable. The lead employee was to make contact with each energized phase with his end of the cable while Employee #1 was to hold his end of the cable in open air for Employee #2 to touch the exposed end with a probe from the multimeter. The lead employee gave the command that he was energizing the cable, and the command was confirmed by Employees #1 and #2. When the multimeter lead made contact with the energized cable, Employee #1 inadvertently made contact with the transformer's protector. An arc flash ensued. The two employees were not wearing arc-rated protective clothing, and Employee #1 was not wearing a face shield. Employee #1 was hospitalized to treat second- and third-degree burns. Employee #2 was hospitalized to treat first degree burns.

Keywords: Burn, E GI II (no ppe), Elec Utility Work, Electric Arc, Electric Arc Flash, Electric Conductor, Electric Meter, Electrical, Electrical Burn, Electrical Testing, Electrical Vault, Face, PPE, Skin, Transformer, Transformer Vault

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 1445072.015 30 M Hospitalized injury Electrical power installers and repairers
2 1445072.015 35 M Hospitalized injury Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close