Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 120553.015 - Employee incurs electric shock after direct contact with ene

Accident Summary Nr: 120553.015 -- Report ID: 0636900 -- Event Date: 10/03/2019
Inspection NrDate OpenedSICNAICSEstablishment Name
1436577.01510/07/2019221119Mastec Services, Inc.

Abstract: At 2:00 p.m. on October 3, 2019, an employee was working as a janitor or cleaner for a firm that provided engineering, building, installation, maintenance and upgrade of energy, utility and communications infrastructure. Its customers are primarily in the utility, communications, and government industries. The employee and two other workers were cleaning an electrical vault. There was a 13.2 kilovolt electrical reactor in the vault. As the employee was cleaning near the reactor, he received an electric shock. He was hospitalized, and his left hand was amputated. The vault cleaning crew had been together for some time. Prior to this incident, the vault cleaning crew had entered and cleaned more than 79 vaults. In this incident, the employee had not been issued and was not wearing electrical protective equipment, such as sleeves and gloves. A language barrier made it difficult for the employer and the employee to communicate what sort of understanding the employee had of a minimum approach distance. His primary language was Spanish. Employees were not briefed on hazards associated with working near 13.2 kilovolt reactors in electrical vaults. Employees conducting cleaning duties inside electrical vaults did not receive briefing on hazards associated with the job, work procedures involved, special precautions, and personal protective equipment.

Keywords: Amputated, Amputation, Cleaning, E GI II (no ppe), Elec Protect Equip, Elec Utility Work, Electric Shock, Electrical, Electrical Burn, Electrical Vault, Electrical Work, Energized, Hand, Housekeeping, PPE, Reactor, Surgical Amputation, Training, Transformer, Transformer Vault, Work Rules

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 1436577.015 58 M Hospitalized injury Janitors and cleaners

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.