Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 116172.015 - Employees are injured by arc flash in electrical panel box

Accident Summary Nr: 116172.015 -- Report ID: 0729300 -- Event Date: 05/08/2019
Inspection NrDate OpenedSICNAICSEstablishment Name
1400166.01505/14/2019332812Rti Advanced Forming Inc.

Abstract: At 2:30 p.m. on May 8, 2019, two employees were working for a firm that provided metal coating, engraving, and allied services to manufacturers. One employee worked as a maintenance electrician. He was checking an electrical panel for burned out fuses. Earlier in the day, he was performing maintenance on the facility's brake oven 8. It was located on the upper level of the facility's fabrication area. The brake oven heated metal parts before they were formed by other fabricating machinery. There was a sudden loss of electrical power to this piece of equipment. The employee went to the "panel bucket" that provided power to brake oven 8 to test the fuses and determine if the power cutoff occurred there. Brake oven 8 ordinarily drew 200 amperes of current at 480 volts. The employee was wearing his arc flash suit over a Level 2 arc flash rated uniform, EH rated boots, safety glasses, ear plugs, a hard hat with a tinted face shield, and suitably rated electrical gloves with leather covers over them. He was not wearing a balaclava. He opened the panel, and drew out his meter from a pocket to test the fuses. One of the meter leads got entangled with a pair of locking pliers, such as Vise-Grips, or channel-lock pliers. The pliers fell into the open bucket, causing an arc flash. The employee suffered first- and second-degree burns over 20 percent of his body. He received severe burns to his chin, throat, and chest. The other employee was processing titanium sheets for the firm's pickle line. This other employee was exposed to nitric oxide and hydrofluoric acid. Both employees were hospitalized. The failure to require a balaclava resulted from a misreading of the NFPA 70E.

Keywords: Chest, Dropped, Electric Arc, Electrical, Electrical Box, Electrical Fault, Electrical Testing, Electrical Work, Electrical panel, Electrician, Energized, Face, Hand Tool, Hydrofluoric Acid, Maintenance, Nitric Acid, PPE, Throat, Training

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 1400166.015 49 M Hospitalized injury Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.