Accident Report Detail
Accident Summary Nr: 101176.015 - Employee is killed by arc flash
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 1280583.015 | 11/14/2017 | 423440 | Certified Restaurant Service Center, Llc |
Abstract: At 1:15 p.m. on November 10, 2017, three employees were to change out a 15 amp breaker from a Square D Power Style switchgear in a 480 volt, 2000 amp 3 phase system. The system was not de-energized. The employee was not wearing the proper PPE to protect himself from electrical shock or arc flash injuries. The employee shorted out the system when his driver, while connecting a conductor to one leg of the three phases, came into contact with the panel causing a short and subsequent arc flash. The employee was transferred to the hospital with critical wounds where he later died.
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 1280583.015 | 72 | M | Fatality | Electricians |