Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 1005172 - ELECTRIC SHOCK - FAILURE TO LOCKOUT LIGHTING CIRCUIT

Accident Summary Nr: 1005172 -- Report ID: 0253670 -- Event Date: 04/26/1990
Inspection NrDate OpenedSICNAICSEstablishment Name
10489833305/01/199045810Jefferson Co Watertown Intl. Airport

Abstract: AN EMPLOYEE WAS REPAIRING A RUNWAY/TAXIWAY LIGHTING SYSTEM. HE WAS ISOLATING CURRENT LEAKS THAT WERE CAUSING DIMMING OF SOME OF THE LIGHTS. TO PERFORM THIS JOB, THE EMPLOYEE LOCKED OUT THE 2400-VOLT LIGHTING SYSTEM AND DUG UP THE LIGHTS. THE SYSTEM WAS RUN AS A 2400-VOLT CIRCUIT LEADING TO UNDERGROUND TRANSFORMERS THAT REDUCED THE VOLTAGE TO 4.5 VOLTS FOR THE LIGHTING FIXTURES. THE EMPLOYEE DUG UP THE DIM LIGHTS DOWN TO THE TRANSFORMERS, CHECKED THE PLUG-IN UNITS, TAPED SOME OF THEM, AND THEN PLACED THEM ON BOARDS. HE REENERGIZED THE 2400-VOLT SYSTEM AND CHECKED OUT THE LIGHTS, MEASURING FOR 4.5 VOLTS AND 5 TO 6 AMPERES AT EACH LIGHT. WITHOUT DEENERGIZING THE SYSTEM AND LOCKING IT OUT, THE EMPLOYEE PLACED THE TRANSFORMERS AND FIXTURE MOUNTS INTO HOLES AND BURIED THEM. HE HAD REPLACED ALL THE LIGHTING STANDARDS AND LIGHTS EXCEPT FOR ONE THAT WAS DAMAGED. THE EMPLOYEE REPLACED THE BREAKAWAY PORTION OF THAT STANDARD AND WAS RECONNECTING THE PLUG TO THE 4.5-VOLT SECONDARY OF THE TRANSFORMER WHEN THE 2400-VOLT PRIMARY, WHICH WAS LEAKING TO GROUND, ARCED TO HIS GLOVES. THE RESULTANT ELECTRIC SHOCK KNOCKED HIM 10 FEET AWAY.

Keywords: LIGHTING CIRCUIT, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, GROUND FAULT, ELECTRIC SHOCK

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 104898333 Non Hospitalized injury Electric Shock Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.