Powered by GoogleTranslate

Inspection Detail

Case Status: CLOSED

Inspection: 1397233.015 - National Grid Electric Services Llc

Inspection Information - Office: Albany Area Office

 

Inspection Nr: 1397233.015
Report ID: 0213100
Date Opened: 05/01/2019

Site Address:
National Grid Electric Services Llc
1699 County Rte 8
Elizaville, NY 12523

Mailing Address:
558 3rd Ave. Ext., Rensselaer, NY 12144

Union Status: Union

SIC:

NAICS: 221122/Electric Power Distribution


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/01/2019

Emphasis:

Case Closed: 12/31/2020


Related Activity
Type Activity Nr Safety Health
Referral 1448919 Yes
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 1 1 2
Initial Penalty $28,415 $0 $0 $0 $0 $28,415
Current Penalty $5,683 $0 $0 $6,630 $0 $12,313
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100132 D01 I 06/25/2019 07/01/2019 $0 $9,472 $0 07/19/2019 F - Formal Settlement Citation has been deleted.
2. 01002 Other 19100269 A04 06/25/2019 04/10/2020 $6,630 $13,260 $0 07/19/2019 F - Formal Settlement  
3. 01003 Serious 19100269 C04 II A 06/25/2019 04/10/2020 $5,683 $5,683 $0 07/19/2019 F - Formal Settlement  

Investigation Summary

Investigation Nr: 115844.015
Event: 04/24/2019
Employee receives shock after touching energized power line

At 2:30 p.m. on April 24, 2019, an employee was working for a utility that distributed electric power. The employer was removing and replacing a 65 foot (19.8 meter) H-frame wooden pole structure in the middle of an apple orchard. The pole carried a 115 kV transmission line. In an effort to work around the apple trees, the employer decided to work within the clear areas between the trees, instead of performing line clearance and removing some trees. The employer had the right-of-way and could have removed trees to provide room to remove and replace the structure without any obstructions. The employee was working as a ground worker. He was on the ground with coworkers aligning poles to be boomed up and installed. Among them was the chief lineman, who was working nearby on the pole truck. The boom truck was operating near low-hanging lines. The lines had been deenergized and grounded. Because the trees made clearance an issue and obstructed the view of the workers, the employee had to hold the outside conductor out of the way of the boom truck. The boom truck operator could then lift a pole between the tree rows. The employee took hold of the line to move it out of the way. He touched it with his bare hands. He was not wearing rubber insulating gloves. Although the line had been grounded and was believed to be deenergized, there was an induced voltage on the line. It had become energized. The employee received a near-fatal electric shock. He lost consciousness, and he suffered burns on his right thumb and right buttock, the entry and exit points for the electric current. He was hospitalized for two or more days.

Keywords: Boom Truck, Burn, E GI II (no ppe), Elec Protect Equip, Elec Utility Work, Electric Shock, Electrical, Energized, Glove, Induced Current, Line Clearance, Maintenance, Obstructed View, Overhead Power Line, PPE, Power Line Worker, Protective Grounding, System Grounding, Training, Tree, Unconsciousness, Utility Pole, Work Rules

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1397233.015 35 M Hospitalized injury
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close