Powered by GoogleTranslate

Inspection Detail

Case Status: CLOSED

Inspection: 1270185.015 - Terry Edwards Plumbing

Inspection Information - Office: Mobile Area Office

 

Inspection Nr: 1270185.015
Report ID: 0418600
Date Opened: 10/04/2017

Site Address:
Terry Edwards Plumbing
Lot 15 Boykin Lakes Loop
Pike Road, AL 36064

Mailing Address:
148 Rocky Top Dr., Deatsville, AL 36022

Union Status: NonUnion

SIC:

NAICS: 238220/ Plumbing, Heating, and Air-Conditioning Contractors


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/05/2017

Emphasis:

Case Closed: 04/09/2018


Related Activity
Type Activity Nr Safety Health
Referral 1276504 Yes
Inspection 1270173 Yes
Inspection 1270170 Yes
Inspection 1269882 Yes
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $3,326 $0 $0 $0 $0 $3,326
Current Penalty $3,326 $0 $0 $0 $0 $3,326
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19261052 C09 02/08/2018 $1,663 $1,663 $0 Z - Issued  
2. 01002 Serious 19261053 B13 02/08/2018 $1,663 $1,663 $0 Z - Issued  
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close