Powered by GoogleTranslate

Inspection Detail

Inspection: 312683857 - Heritage Propane Svcs Corp Dba Pro Flame Of Ramona

Inspection Information - Office: San Diego District Office

 

Inspection Nr: 312683857
Report ID: 0950632
Date Opened: 08/17/2010

Site Address:
Heritage Propane Svcs Corp Dba Pro Flame Of Ramona
1363 Walnut St
Ramona, CA 92065

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:5171

NAICS: 454312/Liquefied Petroleum Gas (Bottled Gas) Dealers


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/29/2010

Emphasis:

Case Closed: 01/18/2011


Related Activity
Type Activity Nr Safety Health
Accident 101462380
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $0 $0 $0 $525 $0 $525
Current Penalty $0 $0 $0 $525 $0 $525
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3203 A 11/03/2010 12/06/2010 $175 $175 $0 -  
2. 01002 Other 3395 E03 11/03/2010 12/06/2010 $175 $175 $0 -  
3. 01003 Other 4650 E 11/03/2010 12/06/2010 $175 $175 $0 -  

Investigation Summary

Investigation Nr: 201075611
Event: 08/16/2010
Propane Gas Worker Is Burned in Gas Burn-Off

Employee #1 was working for a propane services company as a mechanic. He was lighting a propane gas and vapor burn-off tower using an extended-reach-type of lighting device. The burn-off tower was a shop-built device manufactured using schedule 80 pipe and fittings. The tower was equipped with a propane gas orifice. The propane gas supply hose, connection fittings, and valves were designed and approved for propane gas use. The investigation found the following: On the day previous to the accident, Employee #1 used the burn tower to burn off propane vapors from an old customer-owned propane tank that required repairs. It was believed by the employer that an ethyl mercaptan oil residue had accumulated in the customer's propane tank from the years of use and filling. It was believed by the employer that small amounts of ethyl mercaptan oil residue from the customer's propane tank had accumulated in the transfer hose as the propane vapors from the tank were burned off. The transfer hose was used to transfer the propane vapor from the propane tank to the burn tower. At the time of the accident, Employee #1 had connected the transfer hose to a company-owned propane tank and the burn tower. The burn tower was being used to burn off propane vapors from the company propane tank so that repairs could be made to that tank. The burn tower was 87 inches tall. The gas transfer hose and the self-closing valve were connected to the burn tower approximately 12 inches above the ground. Employee #1 was using an Olympian GM 3X continuous ignition flexible butane lighter to light the burn tower. The Olympian GM 3X continuous ignition flexible butane lighter had a 15-inch flexible extension nozzle. The total length of the lighter was 26 inches. Employee #1 was positioned holding the lighter at the burn tower nozzle with one hand. At the same time, he was opening the propane gas valve at the bottom of the burn tower with the other hand. Employee #1 was looking at the top of the tower when the gas ignited. Employee #1 stated that when the gas in the nozzle of the burn tower was ignited, the flame looked like sparklers. Employee #1 released the gas valve handle, causing the gas valve, a self-closing valve, to close, extinguishing the flame. Employee #1 felt the burning sparkler material land on his head and shoulder, and his shirt caught on fire. A coworker observed Employee #1's hair and back on fire. The coworker tackled Employee #1 and rolled him over in a puddle of water to put out the fire. A water hose was also used by others present to further extinguish the fire. Employee #1 was hospitalized.

Keywords: BURN, CLOTHING, MAINTENANCE, FLAMMABLE VAPORS, FIRE, BACK, PROPANE, SPARK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 312683857 Hospitalized injury Burn/Scald(Heat) Heating, air conditioning, and refrig. mechanics
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close