Powered by GoogleTranslate

Inspection Detail

Inspection: 309370195 - Bains Bros Dryer, Billy, Jas, Jabby Bains Partners

Inspection Information - Office: Sacramento District Office

 

Inspection Nr: 309370195
Report ID: 0950621
Date Opened: 09/28/2006

Site Address:
Bains Bros Dryer, Billy, Jas, Jabby Bains Partners
6489 Garden Hwy
Yuba City, CA 95991

Mailing Address:
1970 North Township Rd, Yuba City, CA 95993

Union Status: NonUnion

SIC:2034

NAICS: 311423/Dried and Dehydrated Food Manufacturing


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Health

Close Conference: 03/07/2007

Planning Guide: Health-Manufacturing

Emphasis:

Case Closed: 11/23/2008


Related Activity
Type Activity Nr Safety Health
Accident 102508207
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 1 2 3
Initial Penalty $33,750 $0 $0 $550 $0 $34,300
Current Penalty $12,600 $0 $0 $1,000 $0 $13,600
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3328 B 03/14/2007 04/16/2007 $400 $550 $0 04/19/2007 J - ALJ Decision  
2. 02001 Other 3311 C 03/14/2007 04/16/2007 $600 $14,850 $0 04/19/2007 J - ALJ Decision  
3. 03001 Serious 4530 B 03/14/2007 04/16/2007 $12,600 $18,900 $0 04/19/2007 J - ALJ Decision  

Investigation Summary

Investigation Nr: 202484648
Event: 09/16/2006
Employees Are Burned While Relighting Pilot Light for Dryer

At approximately 9:00 a.m. on September 16, 2006, Employee #1 noticed on his rounds that the dehydration burner in the Oven Number 2 was not operating. He got a pole torch to relight the overhead pilot light. As he entered the tunnel, Employee #2 came to help, if needed. Neither of these employees smelled any natural gas over the background of drying prunes. Neither of the employees had opened the opposite side doors or turned on a fan to ventilate the tunnel of any accumulated gas. As the employees brought the torch near the burner, a fireball erupted, raced to the tunnel opening, catching and burning the both of the employees. No operating flame safeguard system was installed. The employer's UV Eye to detect a pilot light flameout and stop the main natural gas flow was found not working. Employee #1 suffered first and second degree burns to multiple body parts and was treated and released from the local hospital. Employee #2 suffered second and third degree burns and was treated in the Burn Unit for 21 days involving surgery and skin-grafts.

Keywords: BURN, PILOT LIGHT, FIRE, CAUGHT BY, NATURAL GAS, GAS, SMOKE, GAS FITTING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 309370195 Hospitalized injury Burn/Scald(Heat) Laborers, except construction
2 309370195 Hospitalized injury Burn/Scald(Heat) Laborers, except construction
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close