Powered by GoogleTranslate

Inspection Detail

Inspection: 307111351 - Sahara West Library

Inspection Information - Office: Nv-E-Las Vegas 0953220

 

Inspection Nr: 307111351
Report ID: 0953220
Date Opened: 10/21/2003

Site Address:
Sahara West Library
9600 W. Sahara Avenue
Las Vegas, NV 89117

Mailing Address:
3148 N. Buffalo Drive, Las Vegas, NV 89128

Union Status: Union

SIC:8231

NAICS: 519120/Libraries and Archives


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 10/29/2003

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 12/08/2003


Related Activity
Type Activity Nr Safety Health
Accident 101042844
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $375 $0 $0 $0 $0 $375
Current Penalty $375 $0 $0 $0 $0 $375
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 618038502 11/05/2003 12/08/2003 $375 $375 $0 -  

Investigation Summary

Investigation Nr: 201041597
Event: 10/15/2003
Employee Is Not Injured When Boiler Explodes

On October 15, 2003, Employee #1 was modifying a boiler at the Sahara West Library and Fine Arts Museum by installing a MICROTherm Energy Management System (EMS) controller on the side of a Gordon-Piatt control panel and Honeywell control unit. Employee #1 did not have the specific terminal diagram or the MICROTherm instruction manual, only the MICROTherm installation booklet. It, however, did not contain all the information needed to complete the installation safely. Employee #1 incorrectly wired the EMS controller, which allowed gas to build up inside the boiler. When he turned on the boiler, the gas inside the boiler ignited, causing a furnace explosion. The sides of the unit fractured outward, and the front of the boiler was slightly warped. Employee #1 was not injured, because he had been standing next to the front corner of the boiler, out of the path of any flying material.

Keywords: GAS-FIRED BOILER, BOILER, ELECTRICAL WORK, EXPLOSION, ELEC CIRC PART--MISC, ELECTRICAL CABINET, ELECTRICAL BOX

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 307111351 Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.