Powered by GoogleTranslate

Inspection Detail

Inspection: 307028050 - San Diego Marriott At La Jolla

Inspection Information - Office: San Diego District Office

 

Inspection Nr: 307028050
Report ID: 0950632
Date Opened: 05/21/2004

Site Address:
San Diego Marriott At La Jolla
4240 La Jolla Village Dr
La Jolla, CA 92037

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:7011

NAICS: 721110/Hotels (except Casino Hotels) and Motels


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/25/2004

Emphasis:

Case Closed: 10/10/2006


Related Activity
Type Activity Nr Safety Health
Accident 362419582
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 3 5
Current Violations 1 4 5
Initial Penalty $10,120 $0 $0 $1,215 $0 $11,335
Current Penalty $2,700 $0 $0 $900 $0 $3,600
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 461 A 08/30/2004 09/17/2004 $300 $375 $0 I - Informal Settlement  
2. 01002 Other 3320 08/30/2004 09/17/2004 $0 $560 $0 I - Informal Settlement  
3. 01003 Other 23400023 08/30/2004 09/17/2004 $150 $280 $0 I - Informal Settlement  
4. 02001 Serious 5162 C 08/30/2004 09/13/2004 $2,700 $5,060 $0 I - Informal Settlement  
5. 03001 Other 4070 A 08/30/2004 09/13/2004 $450 $5,060 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 201067592
Event: 04/13/2004
Employeei Burned by Solder from Pipe While Working on Motor

On April 13, 2004, an employee, a Senior Engineer, was replacing an electric heater motor for the heater in Room 1037. The employee was working alone, so there were no witnesses, when the motor was being removed. A 0.75-in. copper pipe line was the supply line to the heater, and it carried 180-degree Fahrenheit water at 80 psi. The line broke and sprayed hot water onto the employee's abdomen and groin areas, before the employee could completely unbolt the motor. The pipe came loose from a ball valve. Upon inspection of the ball valve and the pipe leading to the ball valve, it was apparent that the fitting came loose from a bad solder job. The solder job was done upon originally construction of the hotel, in 1985. The copper pipe was only seated into ball valve 0.0625-in. rather than a full seat of 0.75 in. Thus, any little movement or vibration to this poor solder job could have broken the solder joint. When the employee was working on the electric motor, he had turned the supply and return ball valves off. The copper pipe broke off of before supply ball valve, at the joint connection. The investigation showed that the solder joint at the ball valve failed due to a bad solder job, done approximately 20 years prior to this accident. Inspecting the valves prior to work on the electric motor would not been able to visually see any deficiencies in the solder job. The employee was hospitalized and treated for burns.

Keywords: BURN, ABDOMEN, VALVE, PIPE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 307028050 Hospitalized injury Burn/Scald(Heat) Machinery maintenance occupations
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close