Powered by GoogleTranslate

Inspection Detail

Inspection: 305353153 - Valley Detroit Diesel Allison

Inspection Information - Office: Santa Ana District Office

 

Inspection Nr: 305353153
Report ID: 0950631
Date Opened: 01/14/2004

Site Address:
Valley Detroit Diesel Allison
671 W 17th St
Costa Mesa, CA 92627

Mailing Address:
13624 E Nelson Ave, City Of Industry, CA 91746

Union Status: NonUnion

SIC:7389

NAICS: 541990/ All Other Professional, Scientific, and Technical Services


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/02/2004

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 06/29/2005


Related Activity
Type Activity Nr Safety Health
Accident 362472177
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 1 1
Initial Penalty $36,000 $0 $0 $750 $0 $36,750
Current Penalty $0 $0 $0 $300 $0 $300
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3203 A04 B 07/02/2004 07/25/2004 $0 $750 $0 11/16/2004 F - Formal Settlement Citation has been deleted.
2. 02001 Other 2714 A 07/02/2004 07/20/2004 $300 $18,000 $0 11/16/2004 F - Formal Settlement  
3. 03001 Serious 2816 07/02/2004 07/20/2004 $0 $18,000 $0 11/16/2004 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 201145083
Event: 01/14/2004
Worker Is Shocked Servicing a Temporary Power Generator

On January 14, 2004, Employee #1, with Valley Detroit Diesel Allison, a company who rents and setups of high voltage electric generators for temporary power, was contracted by the client to provide additional electrical power to boost up the power available from the utility company, which the client needed to test some special equipment. This client is involved in the manufacture and testing of cryogenic pumps and other parts used in the aerospace industry. The manufacturing and testing operations are housed in a large building. The employer had temporarily wired up additional generators to a transformer owned and maintained by the client. This temporary wiring setup including the generators and the transformer was entirely located outside in the parking area behind the manufacturing building. This testing had been completed and the employer was in the process of dismantling this temporary setup when this incident occurred. The circuits containing generators and the transformer had been completely shut down and there was no live part in the temporary wiring setup. The enclosure that housed this transformer for the temporary setup had three additional cables running through it. These cables were spliced inside this enclosure and had no connection to the transformer. These spliced cables carried Edison 4160VAC power for a 150-horse power motor used by the client as permanent equipment, which was not involved in the temporary wiring setup by the employer. It appears that the transformer enclosure was also used as a junction box for the spliced cables. Each of the spliced connections was covered with pieces of PVC pipe and some duct tape. Before the incident a coworker had tested transformer terminals and determined that there was no power in any part of the transformer. As part of the temporary setup dismantling process, Employee #1 was helping the corker to disconnect the cables from the transformer. While Employee #1 was disconnecting a cable from the transformer, one of the spliced connections was exposed, which started an electrical arc and fire. The right forearm of Employee #1 was burned in the fire before he could get away. Employee #1 suffered third degree burns to his right forearm and was hospitalized for three weeks.

Keywords: BURN, ELECTRIC MOTOR, ELECTRIC ARC, SHOCK, ELECTRICAL WORK, ARM, ELECTRICAL SPLICE, ELECTRIC GENERATOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 305353153 Hospitalized injury Burn/Scald(Heat) Helpers, mechanics and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.