Powered by GoogleTranslate

Inspection Detail

Inspection: 303734099 - Harbor Group Interstate Electrical, Inc.

Inspection Information - Office: Omaha Area Office

 

Inspection Nr: 303734099
Report ID: 0728900
Date Opened: 10/22/2002

Site Address:
Harbor Group Interstate Electrical, Inc.
2911 E Nucor Rd, Rd Box 309
Norfolk, NE 68701

Mailing Address:
1520 North Main, Po Box 260, Sioux Center, IA 51250

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/23/2002

Planning Guide: Safety-Construction

Emphasis: S:Construction, S:Construction Fatalities

Case Closed: 12/27/2002


Related Activity
Type Activity Nr Safety Health
Accident 100051119
Referral 200053635 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $3,750 $0 $0 $0 $0 $3,750
Current Penalty $3,750 $0 $0 $0 $0 $3,750
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A01 11/19/2002 12/02/2002 $1,875 $1,875 $0 -  
2. 01002 Serious 19260416 A03 11/19/2002 12/02/2002 $1,875 $1,875 $0 -  

Investigation Summary

Investigation Nr: 200051886
Event: 10/19/2002
Employee suffers electrical burns from arc flash

On October 19, 2002, Employee #1 was working at a steel manufacturing facility in Norfolk, NE, that was in the process of switching electrical equipment to new transformers. At approximately 7:45 p.m., he entered the electrical room housing the controls, equipment, and switchgear for transformer RT3/RT5 and several DT controls. He performed several tasks in the sequence of establishing and getting RT3 switched to the new designation of RT5. Employee #1 went behind the panel of switchgear and began to remove the back cover to DT3. This switchgear was four units from where he should have been behind RT3. Employee #1 was removing the back cover to DT3 and had pulled it out to a resting position on a temporary angle support 10 to 12 in. from the back of the cabinet. He then reached on top of the cabinet to grab a battery-operated drill to remove the bolt holding the back cover of DT3. He secured the drill and was moving it forward to his position when the battery became loose and dropped inside the switchgear cabinet. Employee #1 reached into the cabinet with his left hand and was retrieving the battery when the drain wire on the center phase pole was pulled loose. It whipped into the air and struck the top phase pole #1, causing an arc flash. Employee #1 suffered electrical burns over 24 percent of his body, including his face, shoulder, upper trunk, arms, and hands. Subsequent investigation determined that he had failed to lockout the DT3, and it was energized at the time of the accident.

Keywords: BURN, PORTABLE POWER TOOL, ELECTRIC ARC, WORK RULES, STRUCK AGAINST, CONSTRUCTION, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC, SWITCHGEAR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 303734099 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close