Powered by GoogleTranslate

Inspection Detail

Inspection: 303204473 - T & W Pole Line Construction, Inc.

Inspection Information - Office: Kansas City Area Office

 

Inspection Nr: 303204473
Report ID: 0728500
Date Opened: 03/06/2000

Site Address:
T & W Pole Line Construction, Inc.
Hwy. C North Of Rayville, Mo
Lawson, MO 64080

Mailing Address:
505 S. Kentucky, Sedalia, MO 65301

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/08/2000

Emphasis: S:Construction Fatalities

Case Closed: 06/26/2000


Related Activity
Type Activity Nr Safety Health
Accident 361887888
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $7,000 $0 $0 $0 $0 $7,000
Current Penalty $0 $0 $0 $3,000 $0 $3,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Other 19260021 B02 06/08/2000 07/19/2000 $0 $7,000 $0 I - Informal Settlement  
2. 01001B Serious 19260950 C01 I 06/08/2000 06/13/2000 $3,000 $0 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 200000925
Event: 03/05/2000
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

An employee was working from the bucket of an aerial lift. He was tying in a new neutral conductor onto an insulator on a bracket on a utility pole. A 13.2-kilovolt (7620-volt phase-to-ground) hot tap was located above the bracket on the same side of the pole. The tap dead-ended about 660 to 760 millimeters from the pole. The employee was not wearing appropriate electrical protective equipment and had not covered the hot tap with insulation. He apparently contacted the tap and was electrocuted.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 303204473 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close