Inspection: 300788411 - Vescor Capital

Inspection Information - Office: San Diego District Office

 

Inspection Nr: 300788411
Report ID: 0950632
Date Opened: 02/13/2002

Site Address:
Vescor Capital
446 26th St
San Diego, CA 92102

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:7349

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/26/2002

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 04/24/2003


Related Activity
Type Activity Nr Safety Health
Accident 362066912
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1 2
Initial Penalty $4,050 $0 $0 $110 $0 $4,160
Current Penalty $4,050 $0 $0 $110 $0 $4,160
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3314 A 09/18/2002 09/23/2002 $110 $110 $0 -  
2. 02001 Serious 23200001 A 09/18/2002 09/23/2002 $4,050 $4,050 $0 -  

Investigation Summary

Investigation Nr: 201065034
Event: 02/11/2002
Workers Are Burned While Repairing Circuit Breaker

At approximately 2:45 p.m. on February 2, 2002, Employee #1 and Employee #2 were trouble shooting a heating, ventilation, and air conditioning (HVAC) system problem and found that the circuit breaker was overheated, and they ultimately attempted to remove it from an energized electrical panel in the electrical room on the roof of the building. Employee #2 reported the problem to the building manager who instructed them to obtain breaker information to order a replacement. When in the electrical room, Employee #1 opened the center panel doors and began to loosen screws on a circuit breaker. Employee #2 questioned Employee #1 about securing electrical power to the panel first. Employee #1 stated that it would just waste time and continued trying to remove the circuit breaker panel. It exploded. Employee #2 moved about 8 to 10 ft away from the panel toward the door. He then saw sparks and observed Employee #1's left hand was unable to let go of the screwdriver he was using that was in contact with the circuit breaker. Employee #2 went to Employee #1, kicked his left shoulder, and broke him loose from the electrical shock condition. Another explosion and fire erupted from the panel. Employee #2 received flash burns to his face and hands as he pulled Employee#1 toward the door. Employee#2 returned to the electrical room and used a nearby fire extinguisher to put out the fire. Employee #1 had departed the roof area and ran into the building yelling and screaming. Several nurses stopped him and administered first aid, and emergency medical services were summoned. Both employees were transported to a local burn center where they were treated for third-degree burns of their faces and hands. Investigation revealed that electrical power had not been secured to the circuit breaker panel. Citations were issued to the company for no lock-out/block-out training and working on energized parts of equipment without meeting required safety conditions.

Keywords: BURN, MAINTENANCE, UNSECURED, ELECTRICAL TESTING, LOCKOUT, CIRCUIT BREAKER, ELECTRIC SHOCK, ELECTRICAL FAULT, FACE, HAND

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 300788411 Hospitalized injury Electric Shock Helpers, mechanics and repairers
2 300788411 Hospitalized injury Other Helpers, mechanics and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close