Inspection: 126638782 - R.S. Harritan & Company, Inc.

Inspection Information - Office: Va-E-Richmond (Regional Office) - Safety 0355111

 

Inspection Nr: 126638782
Report ID: 0355111
Date Opened: 05/01/1997

Site Address:
R.S. Harritan & Company, Inc.
Via Systems / 4500 Laburnum Ave.
Varina, VA 23231

Mailing Address:
, , 00000

Union Status: Union

SIC:1542

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/19/1997

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 01/22/1998


Related Activity
Type Activity Nr Safety Health
Accident 362315897
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $7,000 $0 $0 $0 $0 $7,000
Current Penalty $5,000 $0 $0 $0 $0 $5,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A01 08/20/1997 08/26/1997 $5,000 $7,000 $0 08/28/1997 Y - State Decision  

Investigation Summary

Investigation Nr: 951228
Event: 05/01/1997
ELECTRIC SHOCK - CONTACT WITH LIVE PARTS THRU FISH TAPE

An electrician was using a metal fish tape to pull new conductors through an existing 19-millimeter PVC conduit located next to a grounded metal support. The conduit contained energized conductors supplying a 480-volt motor. He had taped the new conductors to the end of the fish tape, which was bent into a hook. The employee was in a crouched position, leaning against the metal support and pulling the conductor through the conduit. As the fish tape was pulled through a 90-degree bend in the conduit, the hook on the fish tape pierced the insulation on a conductor, which energized the metal fish tape and electrocuted the electrician.

Keywords: ELEC INSULATION, METAL WIRE, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 126638782 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.