Powered by GoogleTranslate

Inspection Detail

Inspection: 105495543 - East Coast Fence

Inspection Information - Office: Sc Department Of Labor, Licensing, And Regulation

 

Inspection Nr: 105495543
Report ID: 0454510
Date Opened: 03/12/1990

Site Address:
East Coast Fence
Fraser St.
Georgetown, SC 29442

Mailing Address:
P. O. Box 1112, Georgetown, SC 29440

Union Status: NonUnion

SIC:1799

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/20/1990

Emphasis:

Case Closed: 04/26/1990


Related Activity
Type Activity Nr Safety Health
Accident 360282404
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 4 5
Current Violations 1 4 5
Initial Penalty $480 $0 $0 $0 $0 $480
Current Penalty $480 $0 $0 $0 $0 $480
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260957 A02 03/26/1990 03/29/1990 $480 $480 $0 -  
2. 02001 Other 19260059 E01 03/26/1990 04/27/1990 $0 $0 $0 -  
3. 02002 Other 19260059 E01 I 03/26/1990 04/27/1990 $0 $0 $0 -  
4. 02003 Other 19260059 G01 03/26/1990 04/27/1990 $0 $0 $0 -  
5. 02004 Other 19260059 H 03/26/1990 04/27/1990 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 908012
Event: 10/04/1989
BURN - FAULT ON OVERHEAD LINE IN SUBSTATION

THREE EMPLOYEES OF A FENCING CONTRACTOR WERE REMOVING AN OLD FENCE SO THAT THEY COULD INSTALL A NEW FENCE AROUND A SUBSTATION AT A STEEL PLANT. ONE OF THE EMPLOYEES CLIMBED TO THE TOP OF A WOODEN LADDER AGAINST THE EXISTING 6-FOOT-HIGH, GROUNDED METAL FENCE. SOME 13.8-KILOVOLT BUSBARS WERE LOCATED WITHIN THE SUBSTATION, 40 INCHES FROM THE FENCE AND 8 FEET, 1 INCH ABOVE THE GROUND. THE EMPLOYEE ON THE LADDER BEGAN USING PLIERS TO REMOVE THE OLD FENCE. A SECOND EMPLOYEE, WHO HAD BEEN HOLDING THE LADDER, TURNED TO WALK TOWARD THE CREW'S TRUCK, WHICH WAS PARKED NEAR THE FENCE. THE THIRD EMPLOYEE WAS STANDING AT THE TRUCK. THE BUS ARCED, AND ALL THREE EMPLOYEES WERE BURNED. THEY HAD BEEN WORKING TOO CLOSE TO THE BUS. THE EMPLOYEES WERE HOSPITALIZED FOR THEIR INJURIES.

Keywords: BURN, CLOTHING, OVERHEAD POWER LINE, ELECTRICAL, LADDER, E PTD, SUBSTATION, ELEC UTILITY WORK, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 105495543 Hospitalized injury Burn/Scald(Heat) Assemblers
2 105495543 Hospitalized injury Burn/Scald(Heat) Assemblers
3 105495543 Hospitalized injury Burn/Scald(Heat) Assemblers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.