Powered by GoogleTranslate

Inspection Detail

Inspection: 105483895 - Springs Mills Frances Plant

Inspection Information - Office: Sc Department Of Labor, Licensing, And Regulation

 

Inspection Nr: 105483895
Report ID: 0454510
Date Opened: 07/05/1989

Site Address:
Springs Mills Frances Plant
Hwy #9
Ft. Lawn, SC 29714

Mailing Address:
P.O. Box 70, Ft. Mill, SC 29704

Union Status: NonUnion

SIC:2221

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/02/1989

Emphasis:

Case Closed: 04/17/1990


Related Activity
Type Activity Nr Safety Health
Accident 360283394
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $700 $0 $0 $0 $0 $700
Current Penalty $350 $0 $0 $0 $0 $350
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 10012 A 08/23/1989 08/26/1989 $350 $700 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 800797
Event: 06/10/1989
EMPLOYEE BURNED EXPLODING STEAM

Employee #1 and coworker were changing a gasket in a steam line. Employee #1 entered a pit 3.5-ft by 10-ft deep using a ladder to loosen the bolts so that any water steam pressure could drain off. Employee #1 cut off the steam the day before on the boiler and locked onto when he thought it was drained. He returned to the pit to remove the bolts and replace the gasket. The coworker removed the ladder to allow work room and lowered a drop light. When Employee #1 removed the bolts, there was an explosion of steam and water. Employee #1 tried to climb out using the droplight until he received assistance. He received second and third degree burns to his chest, abdomen and legs. The trap on the bottom of the pit was found to be defective and there were no pressure gauges.

Keywords: BURN, CHEST, STEAM LINE, ABDOMEN, GASKET, BOILER, STEAM, EXPLOSION, LEG

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 105483895 Hospitalized injury Burn/Scald(Heat) Not specified mechanics and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close