• Part Number:
    1910
  • Part Number Title:
    Occupational Safety and Health Standards
  • Subpart:
    1910 Subpart L
  • Subpart Title:
    Fire Protection
  • Standard Number:
  • Title:
    Fixed extinguishing systems, gaseous agent.
  • GPO Source:
1910.162(a)

Scope and application -

1910.162(a)(1)

Scope. This section applies to all fixed extinguishing systems, using a gas as the extinguishing agent, installed to meet a particular OSHA standard. These systems shall also comply with § 1910.160. In some cases, the gas may be in a liquid state during storage.

1910.162(a)(2)

Application. The requirements of paragraphs (b)(2) and (b)(4) through (b)(6) shall apply only to total flooding systems.

1910.162(b)

Specific requirements.

1910.162(b)(1)

Agents used for initial supply and replenishment shall be of the type approved for the system's application. Carbon dioxide obtained by dry ice conversion to liquid is not acceptable unless it is processed to remove excess water and oil.

1910.162(b)(2)

Except during overhaul, the employer shall assure that the designed concentration of gaseous agents is maintained until the fire has been extinguished or is under control.

1910.162(b)(3)

The employer shall assure that employees are not exposed to toxic levels of gaseous agent or its decomposition products.

1910.162(b)(4)

The employer shall assure that the designed extinguishing concentration is reached within 30 seconds of initial discharge except for Halon systems which must achieve design concentration within 10 seconds.

1910.162(b)(5)

The employer shall provide a distinctive pre-discharge employee alarm capable of being perceived above ambient light or noise levels when agent design concentrations exceed the maximum safe level for employee exposure. A pre-discharge employee alarm for alerting employees before system discharge shall be provided on Halon 1211 and carbon dioxide systems with a design concentration of 4 percent or greater and for Halon 1301 systems with a design concentration of 10 percent or greater. The pre-discharge employee alarm shall provide employees time to safely exit the discharge area prior to system discharge.

1910.162(b)(6)
1910.162(b)(6)(i)

Where egress from an area cannot be accomplished within one minute, the employer shall not use Halon 1301 in concentrations greater than 7 percent.

1910.162(b)(6)(ii)

Where egress takes greater than 30 seconds but less than one minute, the employer shall not use Halon 1301 in a concentration greater than 10 percent.

1910.162(b)(6)(iii)

Halon 1301 concentrations greater than 10 percent are only permitted in areas not normally occupied by employees provided that any employee in the area can escape within 30 seconds. The employer shall assure that no unprotected employees enter the area during agent discharge.

[45 FR 60712, Sept. 12, 1980; 46 FR 24557, May 1, 1981]