|
||||
![]() |
||||
| Electric Power >> Hazardous Energy Control >>
Portable Grounding Equipment Hazardous Energy Control Portable Grounding Equipment Portable grounding cables and clamps must be able to carry and withstand the
maximum fault current available for the time needed for an overcurrent device to
trip. The amount of available fault current needs to be determined; depending on
the amount, two or more leads in parallel may need to be installed. See 1910.269(n)(4).Each grounding cable installed on transmission and primary voltage distribution systems must be at least a #2 copper (or equivalent). On secondary voltage systems (600 volts and less), ground leads must be sized so that they are larger than the conductor and have an impedance low enough so that the operation of any protective device is not delayed. For guidance, see CPL 02-01-038, Appendix B, Item 11. ![]() Clamps and Cables The clamps on ground leads are a critical component and are much larger than common distribution connectors (such as hotline clamps or bolted connectors) due to the large amount of current that needs to be carried. Some critical factors to consider are:
Grounding for Employee Protection Protective Grounding and Bonding Insulating Protective Equipment (IPE) |
||||
|
||||

Newsletter
RSS Feeds
Print This Page
Text Size


Portable grounding cables and clamps must be able to carry and withstand the
maximum fault current available for the time needed for an overcurrent device to
trip. The amount of available fault current needs to be determined; depending on
the amount, two or more leads in parallel may need to be installed. See 
