Powered by GoogleTranslate
Standard Interpretations - (Archived) Table of Contents
• Standard Number: 1910.107
• Status: Archived

Archive Notice - OSHA Archive

NOTICE: This is an OSHA Archive Document, and may no longer represent OSHA Policy. It is presented here as historical content, for research and review purposes only.

July 28, 1997

Mr. Samir Karandikar
EPSON Industrial Systems
P.O. Box 7060
The Woodlands, TX 77387

Dear Mr. Karandikar:

This is in response to your September 12, 1996 letter requesting an interpretation of 29 CFR 1910.107(d)(9), air exhaust requirements for spray finishing using flammable and combustible materials. Please accept our apology for the delay in responding. Your request and our reply follow:

Request:

Please confirm the Occupational Safety and Health Administration (OSHA) interpretation in the OSHA August 27, 1991 letter to Mr. Tom Ellis of Classic Systems, Inc. which stated that employers who fully comply with the specifications and requirements of the National Fire Protection Association standard NFPA-33-1989, concerning the recirculation of exhaust air to an occupied spray booth, would not be cited under 29 CFR 1910.107(d)(9).

Reply:

This letter reconfirms the interpretation in the OSHA letter you referenced above. Employers who fully comply with the specifications and requirements of the National Fire Protection Association standard NFPA 33-1995 (previously, NFPA 3301989) concerning the recirculation of exhaust air to an occupied spray booth would not be cited under 29 CFR 1910.107(d)(9).

We appreciate your interest in Occupational Safety and Health. If we can be of further assistance, please contact the Office of Safety Compliance Assistance, Mr. Ronald Davies, telephone (202) 219-8031, ext. 110.

Sincerely,

John B. Miles, Jr., Director
Directorate of Compliance Programs

Archive Notice - OSHA Archive

NOTICE: This is an OSHA Archive Document, and may no longer represent OSHA Policy. It is presented here as historical content, for research and review purposes only.

Standard Interpretations - (Archived) Table of Contents

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close