• Standard Number: 1910.263(l)(9)(iv)(a)

December 13, 1994

Dick Kozyra, President
American Bakers Cooperative, Inc.
122 Randolph Ave., Suite 202
P.O. Box 308
Clifton, NJ 07001

Dear Mr. Kozyra:

This is in further response to your May 31, letter requesting interpretation of the Bakery Equipment Standard, 29 CFR 1910.263(l)(9)(iv)(a). Please accept our apology for the delay in re-sponding.

You requested clarification for ovens with time delay relay systems built into the power supply line, which is interlocked with the fuel safety valves. Specifically, you asked if all gas safeties, when tripped, must cause the gas safety valves to close immediately, or is a time delay legal?

The standard does not allow employers to install time delay relay systems in the power control line of ovens, when the power line is interlocked with the fuel supply.

The high-tension current for any electric spark-type ignition device must originate in a power supply line which is interlocked with the fuel line supply for the oven in such a way that in case of current failure both the source of electricity to the high tension circuits and the fuel supply shall be turned off simultaneously.

We appreciate your interest in employee safety and health. If we can be of further assistance please contact Mr. Russelle R. McCollough in the Office of General Industry Compliance Assistance, telephone number (202) 219-8031, extension 105.

Sincerely,

John B. Miles, Jr., Director
Directorate for Compliance Programs


Standard Interpretations - Table of Contents

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.