SUBJECT:            Defective Stub Ends Which Have Been or May Be
                   Installed in Work Place Piping Systems
The following comments are provided on review of documentation provided concerning the evaluation and testing of stainless steel stub ends.

1. Several (named) foreign manufacturers produced defective piping stub ends ranging in size from 1/2 to 6 inches (1.27 - 15.24 cm) in diameter. These defective stub ends which were introduced into the U.S. marketplace were discovered by employers to be installed in piping systems in their work places.

2. The defective stub ends lacked full penetration welds due to poor fit-up, that is, excessive space between the stub neck and flange. The cause of the poor fit-up could be caused by deficient welding procedures, lack of supervision to ensure that acceptable welding procedures are followed or use of unqualified welders. Shipping defective stub ends could be the end result of deficient quality control (inspections and testing) or other reasons.

3. Since certification (stub ends stamped with ASTM A403) by manufacturers supplying the defective stub ends is not reliable, follow-up quality control must be provided by intermediate suppliers or end users (employers).

4. Fatigue testing results indicate that stub ends without full penetration welds will fail much earlier than those with full penetration welds (required by ASTM A403).

5. Normally, OSHA expects an employer to determine, through information provided by the manufacturer (supplier), machine or equipment quality to ensure safe work place use in compliance with OSHA safety and health requirements. This determination includes information provided by foreign manufacturers. Therefore, a safety alert on these defective stub ends is deemed appropriate.
Archive Notice - OSHA Archive

NOTICE: This is an OSHA Archive Document, and may no longer represent OSHA Policy. It is presented here as historical content, for research and review purposes only.

Standard Interpretations - (Archived) Table of Contents

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close