February 6, 1980

MEMORANDUM FOR: ALFRED BARDEN
REGIONAL ADMINISTRATOR

THRU: ROGER CLARK
Field Coordinator

FROM: GROVER C WRENN
Director, Federal Compliance and State Programs

SUBJECT: Use of Steel Bandings as Guardrails


This is in response to your earlier memorandum on the above subject.

29 CFR 1926.500(f)(1)(vi), for temporary or emergency conditions, states that other types, sizes and arrangements of railing construction are acceptable, provided they meet the requirements contained in (a), (b), (c) and (d). The standard permits the use of any material meeting the above requirements.

The use of the word "normally" was included in the memorandum to clarify that the metal banding thickness usually requires the edges to be rolled, covered or otherwise shielded to protect employees that may make sudden contact with the edges.

In situations where the span between columns exceeds ten feet, it may be difficult to provide enough tension in a steel band to keep the level of deflection at a minimum while withstanding a two-hundred pound force.

On many construction projects when wire rope is used for the top and intermediate rails, employers are confronted with a similar difficulty in providing enough tension on the rope to minimize the deflection. The compliance officers making construction inspections are required to evaluate the wire rope and the metal banding systems during the course of an inspection. In this regard, plans are in progress to provide the field staff with force measurement equipment to evaluate such systems.

Subpart R, 29 CFR 1926.750 allows the use of 1/2 inch wire rope or equal, to be installed around the periphery of temporary planked or metal decked floors during structural steel assembly. Steel bands providing equivalent strength could be used in lieu of the 1/2 wire rope, provided the metal banding edge is rolled, covered or otherwise protected.



Archive Notice - OSHA Archive

NOTICE: This is an OSHA Archive Document, and may no longer represent OSHA Policy. It is presented here as historical content, for research and review purposes only.

Standard Interpretations - (Archived) Table of Contents

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close