March 4, 1977

Mr. James Wolf Manager,
Government Relations
The Trane Company
2020 14th Street
North Arlington, Virginia 22201

Dear Mr. Wolf:

This is in response to your letter dated February 4, 1977, and confirms the telephone conversations with Harold Gier, Safety Specialist, Division of Occupational Safety Programming, concerning machinery and machine guarding.

In answer to your first question; the intent of 29 CFR 1910.212(a)(5), fan blade guarding requirement, is to prevent an employee from coming into contact with a blade and the size opening in the guard is dependent on the distance between the blade and the guard. This standard was intended to apply only to fans used for employee comfort cooling.

The standard was not intended to apply to fans that are an integral part of a unit such as cooling towers, air handling units, or in closed ventilating systems. However, fans of the latter type are required to be guarded in accordance with 29 CFR 1910.212(a)(1), as rotating parts. The guidelines for the construction of the guards are found in paragraphs (m) and (o) of 29 CFR 1910.219 using Table 0-12 to determine material, distance and size of openings required.

In answer to your second question; the primary concern of "enclosed" and "fully enclosed" is to prevent employees from injuries by moving belts, taking into consideration guarding by location. Enclosed on vertical and inclined belts means that only that part of the belt less than seven (7) feet from the floor must be guarded, while any other part of the belt over seven (7) feet may remain exposed. Full enclosure of horizontal belts with both runs less than 42 inches above the floor is required, meaning all exposed sides including the full length of the belts. A full length, three-sided guard is considered as meeting the intent of the standard as long as the fourth side is guarded by location.

Hopefully, this information will be helpful. If I may be of any further assistance, please feel free to contact me.

Sincerely,



John K. Barto,
Chief Division of
Occupational Safety Programming



Archive Notice - OSHA Archive

NOTICE: This is an OSHA Archive Document, and may no longer represent OSHA Policy. It is presented here as historical content, for research and review purposes only.

Standard Interpretations - (Archived) Table of Contents

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close