December 18, 1975

Mr. Richard P. Landers
Manager Labor Relations
Gould Pumps, Inc.
Seneca Falls, New York 13146

Dear Mr. Landers:

This is in response to your letter requesting a clarification of OSHA standards on means of egress.

Reviewing the OSHA standards 1910.35, 1910.36 and 1910.37, we find significant passages which specify exactly how means of egress shall be located and identified. 1910.35(a) defines a means of egress an a continuous and unobstructed way of exit travel in vertical and horizontal plans. 1910.36(b)(1) requires exits sufficient to permit prompt escape not dependent solely on any single safeguard. 1910.36(b)(5) requires that exits and means of exit shall be clearly identified and those doors or corridors not leading directly to an exit discharge shall be identified by signs or other means as "Not an Exit" or similar wording. Table El (page 23532 of Federal Register dated June 27, 1974 Volume 39 #125) requires that space occupied by 60 or less persons shall have passages 30 to 44 inches wide and space occupied by 100 or more persons shall be provided with passageways greater than 44 inches.

All interpretations of OSHA standards are subject to the compliance officer's evaluation while making a physical inspection of a premises. However, assembling the preceding information, we find the following as one of several means of complying with OSHA standards: (a) passage through the warehouse area could be permitted if the entry door is identified as "Not an Exit" and there are at least two additional means of egress from each of the buildings mentioned in your letter, (b) if not more than 60 persons occupy the adjoining buildings, the passageway would meet the OSHA standard of 36 inches minimum, but if occupied by more than 60 persons (75 persons by your letter), the passageway and entry doors would have to meet part (a) of this paragraph.

We have mailed several OSHA brochures including the Federal Register noted above under separate cover.

Sincerely,



Alfred Barden
Assistant Regional Director
Occupational Safety and Health

Archive Notice - OSHA Archive

NOTICE: This is an OSHA Archive Document, and may no longer represent OSHA Policy. It is presented here as historical content, for research and review purposes only.

Standard Interpretations - (Archived) Table of Contents

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close