Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Case Status: CLOSED
Inspection: 76936.015 - First Energy/Ohio Edison Company

Inspection Information - Office: Cleveland

Nr: 76936.015Report ID: 0522300Open Date: 05/21/2011

First Energy/Ohio Edison Company
733 Tell Dr.
Canal Fulton, OH 44614
Union Status: Union
SIC:
NAICS: 221122/Electric Power Distribution
Mailing: 2600 Erie Steet S, Massillon, OH 44646

Inspection Type:Fat/Cat
Scope:Complete Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:05/21/2011
Close Case:05/26/2015

Related Activity:TypeIDSafetyHealth
 Accident48040 Yes  
Case Status: CLOSED

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 2 2
Initial Penalty $28,000 $0 $0 $0 $0 $28,000
Current Penalty $14,000 $0 $0 $0 $0 $14,000
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Serious 19100269 A03 11/08/2011 01/01/2013 $7,000 $7,000 $0 12/05/2011 F - Formal Settlement
Deleted 2. 01002 Serious 19100269 C01 11/08/2011 11/23/2011 $0 $7,000 $0 12/05/2011 F - Formal Settlement
  3. 01003 Serious 19100269 N02 11/08/2011 01/01/2013 $7,000 $7,000 $0 12/05/2011 F - Formal Settlement
Deleted 4. 01004 Serious 19100269 N05 11/08/2011 12/01/2011 $0 $7,000 $0 12/05/2011 F - Formal Settlement

Accident Investigation Summary
Summary Nr: 2687.015Event: 05/21/2011Employee Is Electrocuted While Repairing Underground Power L
At noon on May 21, 2011, a crew was removing a section of an underground power line to repair a power outage at an underground installation in a subdivision. The crew discovered that the fault was located under a driveway, so they parked the lines/feeders in the transformers, located and dug up the line on both sides of the driveway. An employee performed a spike test to ensure that the line/feeder was deenergized. The crew then cut the line/feeder and attempted without success to pull a new section using the old line under the driveway. After a string out procedure was performed, they back fed the line that was faulted under the driveway. The crew did not test the line/feeder to ensure it was still deenergized after powering the transformers. The lines were not marked and employees energized the line they were repairing. The employee entered the trench to strip the line to accept the new line being spliced into it and was electrocuted after grabbing it.
Keywords: electrical
Inspection Degree Nature Occupation
1 76936.015 Fatality Electric Shock Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.