Inspection: 315480301 - Monroe Drywall Construction, Inc.

Inspection Information - Office: Jacksonville

Nr: 315480301Report ID: 0419700Open Date: 09/28/2011

Monroe Drywall Construction, Inc.
535 W. 23rd Street
Panama City, FL 32405
Union Status: NonUnion
SIC: 1742/Plastering, Drywall, Acoustical, and Insulation Work
NAICS: 238310/Drywall and Insulation Contractors
Mailing: 19211 Panama City Beach Parkway, Panama City Beach, FL 32413

Inspection Type:Accident
Scope:Complete Advanced Notice:Y
Ownership:Private
Safety/Health:Safety Close Conference:09/30/2011
Emphasis: S:Commercial Constr, S:ElectricalClose Case:08/27/2014

Related Activity:TypeIDSafetyHealth
 Accident101358653    

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 2 1 3
Initial Penalty $6,600 $0 $0 $0 $0 $6,600
Current Penalty $600 $0 $0 $0 $0 $600
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
Deleted 1. 01001A Serious 19260020 B01 01/24/2012 03/09/2012 $0 $2,400 $0 02/16/2012 J - ALJ Decision
  2. 01001B Serious 19260021 B02 01/24/2012 03/09/2012 $200 $0 $0 02/16/2012 J - ALJ Decision
  3. 01002 Serious 19260416 A03 01/24/2012 01/27/2012 $400 $4,200 $0 02/16/2012 J - ALJ Decision
  4. 02001 Other 19101200 E01 01/24/2012 03/09/2012 $0 $0 $0 02/16/2012 J - ALJ Decision

Accident Investigation Summary
Summary Nr: 201354248Event: 09/27/2011Drywall Installer Is Electrocuted
On September 27, 2011, Employee #1 was in a store being remodeled, clearing an area to stack drywall sheets. He was electrocuted when he contacted an energized 480 volt wire that was protruding from a conduit on an adjacent wall. The conduit had been broken during the demolition of an existing wall ten days prior to the incident. The end of the wire had been capped with a wire nut, and the circuit breaker had been turned off; however, the breaker had not been locked out or secured.
Keywords: demolition, conduit, electric cable, electrocuted, construction, circuit breaker
Inspection Degree Nature Occupation
1 315480301 Fatality Electric Shock Drywall installers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.