Inspection: 314489030 - Saxon Drilling L.P. Rig 140

Inspection Information - Office: Little Rock

Nr: 314489030Report ID: 0627100Open Date: 05/18/2010

Saxon Drilling L.P. Rig 140
Stroud 09-13 #6-34h27
Damascus, AR 72039
Union Status: NonUnion
SIC: 1381/Drilling Oil and Gas Wells
NAICS: 213111/Drilling Oil and Gas Wells
Mailing: 1500 Museum Rd. Ste. 105, Conway, AR 72032

Inspection Type:Accident
Scope:Partial Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:05/18/2010
Emphasis: L:Oilgas, S:ElectricalClose Case:07/07/2011

Related Activity:TypeIDSafetyHealth
 Accident100265552    

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 1 1
Initial Penalty $18,000 $0 $0 $0 $0 $18,000
Current Penalty $4,500 $0 $0 $0 $0 $4,500
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Serious 19100304 G05 10/29/2010 11/10/2010 $4,500 $4,500 $0 11/19/2010 F - Formal Settlement
Deleted 2. 01002A Serious 19100332 B01 10/29/2010 11/10/2010 $4,500 $4,500 $0 11/19/2010 F - Formal Settlement
Deleted 3. 01002B Serious 19100333 C02 10/29/2010 11/10/2010 $0 $0 $0 11/19/2010 F - Formal Settlement
Deleted 4. 01003 Serious 19100333 A01 10/29/2010 11/10/2010 $4,500 $4,500 $0 11/19/2010 F - Formal Settlement
Deleted 5. 01004 Serious 19100335 A01 I 10/29/2010 11/10/2010 $4,500 $4,500 $0 11/19/2010 F - Formal Settlement

Accident Investigation Summary
Summary Nr: 200263879Event: 05/17/2010Employee Is Electrocuted While Setting Up Rig
On May 17, 2010, employees were setting up Saxon Drilling Rig Number 140, in Damascus, AR. The employees were connecting power lines to the generator house, while the generator was running without proper grounding. One employee was on the ground, throwing the male end of a 277-volt, three-phase hook-up line from the "M.C.C." (apparently motor control center) to Employee #1, who was on top of the generator house. The employee on the ground noticed that Employee #1 was not standing. Employee #1 had been electrocuted by backfeed through the M.C.C. The employee on the ground and other employees rushed to Employee #1 and administered CPR, until EMS arrived. Employee #1 was carried to Ozark Health Medical Center in Clinton, where he was pronounced dead.
Keywords: cpr, electrocuted, oil well drilling, electrical work, lockout, set up, gas well drilling, electric generator
Inspection Degree Nature Occupation
1 314489030 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.