Inspection: 313508442 - Butterfly Wendel Us, Inc. Dba Deutsch Ecd

Inspection Information - Office: Ca San Bernardino

Nr: 313508442Report ID: 0950633Open Date: 05/06/2010

Butterfly Wendel Us, Inc. Dba Deutsch Ecd
5733 West Whittier Avenue
Hemet, CA 92545
Union Status: NonUnion
SIC: 3629/Electrical Industrial Apparatus, Not Elsewhere Classified
NAICS: 335999/All Other Miscellaneous Electrical Equipment and Component Manufacturing

Inspection Type:Accident
Scope:Partial Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:09/28/2010
Planning Guide: Safety-Manufacturing Close Case:02/11/2011
Emphasis: L:Arrastim

Related Activity:TypeIDSafetyHealth
 Accident102612223    

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 1 2 3
Current Violations 1 2 3
Initial Penalty $18,000 $0 $0 $560 $0 $18,560
Current Penalty $2,700 $0 $0 $560 $0 $3,260
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Other 3203 A03 09/28/2010 10/29/2010 $185 $185 $0 -
  2. 01002 Other 3314 G02 09/28/2010 10/29/2010 $375 $375 $0 -
  3. 02001 Serious 23200004 A02 09/28/2010 10/11/2010 $2,700 $18,000 $0 10/12/2010 F - Formal Settlement

Accident Investigation Summary
Summary Nr: 202613204Event: 04/07/2010Electric Arc Flash Burns Employee'S Face And Arm
At approximately 3:15 a.m. on April 7, 2010, Employee #1 was going to replace a 100-amp main fuse of a 3 phase 480-volt, Circuit Breaker Box #2, located in the Electrical Power room. The circuit breaker was connected to an Electrical Lighting Panel (LPB) powering the lighting systems of Molding & Assembly Departments of the manufacturing facility. He opened the circuit breaker cover and checked the continuity of the fuses utilizing a Fluke multi-meter tester. He determined that one of the three fuses were "Bad", which was replaced on April 6, 2010, in 2nd shift. He was in the process of replacing the fuse by using a non-conductive Buss Fuse Puller (Manufacturing Little Fuse, Model Number #FP-3) without deenergizing the circuit breaker when it started sparking causing electrical flash injuring him seriously. Employee #1 suffered burn injuries of his face and right lower arm. Employee #1 was taken to Arrowhead Regional Medical Center for treatment. Employee #1 was hospitalized for five days. The employer reported the serious injury accident to the Division at 8:31 a.m. on April 7, 2010.
Keywords: burn, fuse, electric arc, maintenance, electrician, mechanic, circuit breaker, flashback, arm, face
Inspection Degree Nature Occupation
1 313508442 Hospitalized injury Burn/Scald(Heat) Machinery maintenance occupations

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close