Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 313164196 - James Swofford Dba Swofford Electric

Inspection Information - Office: Ca Santa Ana District Office

Nr: 313164196Report ID: 0950631Open Date: 02/25/2010

James Swofford Dba Swofford Electric
21730 Newland Street
Huntington Beach, CA 92646
Union Status: NonUnion
SIC: 1731/Electrical Work
NAICS: 238210/Electrical Contractors
Mailing: 7372 Walnut St #M, Buena Park, CA 90620

Inspection Type:Accident
Scope:Partial Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:04/29/2010
Close Case:02/05/2019

Related Activity:TypeIDSafetyHealth
 Accident102589389    

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 2 2 4
Current Violations 2 2 4
Initial Penalty $13,950 $0 $0 $455 $0 $14,405
Current Penalty $11,700 $0 $0 $360 $0 $12,060
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Other 1509 B 06/22/2010 06/25/2010 $260 $260 $0 07/16/2010 -
  2. 01002 Other 29400001 A 06/22/2010 06/25/2010 $100 $195 $0 07/16/2010 J - ALJ Decision
  3. 02001 Serious 2940 C 06/22/2010 06/25/2010 $900 $3,150 $0 07/16/2010 J - ALJ Decision
  4. 03001 Serious 29400009 06/22/2010 06/25/2010 $10,800 $10,800 $0 07/16/2010 J - ALJ Decision

Accident Investigation Summary
Summary Nr: 202551560Event: 02/11/2010Burn - Electrical Fault In Voltage Meter
Two employees of an electrical contractor went to a site to wipe down surfaces and vacuum the bottoms of 4,160-volt cubicles in an electrical room. They had a rag and Simple Green cleaning fluid. Neither employee had previously worked on equipment of this voltage, and the employees did not know the operating voltage of the equipment. The onsite employer racked out and locked the equipment to be cleaned, and Employee #1, an electrician, did a walk down with the employer to verify that the equipment was racked out. However, the two employees did not know that one of the cubicles remained energized from another source of electric energy. On the door of that cubicle was a red-stenciled sign that read, "CAUTION MAY BE ENERGIZED FROM AN ALTERNATE SOURCE." Neither employee noticed the sign, and the onsite employer did not mention the alternate energy source to the employees. The following day, after meeting with the onsite employer, the employees began to clean the cubicles. When Employee #2 was cleaning the still-energized cubicle, he felt a slight electric shock. He took out a 600-volt proximity tester, and it lit up without touching the conductors. Employee #1 retrieved a voltage meter rated for 750 volts and placed the meter leads on the conductors. The meter failed and the ensuing electric arc burned both employees. Employee #1 received second- and third-degree burns. He underwent skin graft surgery and was hospitalized for his injuries. Employee #2 was hospitalized for more than 24 hours. He received pain medication for his burns. (The original form did not list Employee #2 on an injury line.)
Keywords: burn, electric arc, e gi iv, electrical, electrician, electrical work, lockout, test equipment, circuit breaker, electrical fault
Inspection Degree Nature Occupation
1 313164196 Hospitalized injury Burn/Scald(Heat) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.