Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 311815492 - All American Air, Inc.

Inspection Information - Office: Jacksonville

Nr: 311815492Report ID: 0419700Open Date: 05/22/2008

All American Air, Inc.
1008 W. International Speedway Blvd.
Daytona Beach, FL 32114
Union Status: NonUnion
SIC: 1711/Plumbing, Heating and Air-Conditioning
NAICS: 238220/ Plumbing, Heating, and Air-Conditioning Contractors
Mailing: 661a Commerical Drive, Holly Hill, FL 32117

Inspection Type:Accident
Scope:Complete Advanced Notice:Y
Ownership:Private
Safety/Health:Safety Close Conference:06/13/2008
Emphasis: L:Fall, S:Commercial Constr, S:Electrical, S:Fall From HeightClose Case:10/15/2008

Related Activity:TypeIDSafetyHealth
 Accident101356889    

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 5 5
Initial Penalty $17,700 $0 $0 $0 $0 $17,700
Current Penalty $10,500 $0 $0 $0 $0 $10,500
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001A Serious 19260021 B02 08/26/2008 09/08/2008 $3,000 $4,900 $0 I - Informal Settlement
  2. 01001B Serious 19260503 A01 08/26/2008 08/29/2008 $0 $0 $0 I - Informal Settlement
  3. 01002A Serious 19260416 A01 08/26/2008 09/03/2008 $3,000 $4,900 $0 I - Informal Settlement
  4. 01002B Serious 19260416 A03 08/26/2008 09/03/2008 $0 $0 $0 I - Informal Settlement
  5. 01003 Serious 19260417 A 08/26/2008 08/29/2008 $3,000 $4,900 $0 I - Informal Settlement
  6. 01004 Serious 19260501 B01 08/26/2008 09/03/2008 $750 $1,500 $0 I - Informal Settlement
  7. 01005 Serious 19260501 B04 I 08/26/2008 08/29/2008 $750 $1,500 $0 I - Informal Settlement

Accident Investigation Summary
Summary Nr: 201353588Event: 05/21/2008Employee Is Electrocuted In Air Handling Equipment
On May 21, 2008, Employee #1 was with a crew installing a steel security grate inside the duct system of a 10-ton Trane air conditioning system (Model Number THC120A4RGAOW2B, Serial Number 8044100711L) that was located on a roof. As he crawled into the duct to weld the grate into place, the back of his head contacted an energized heat strip on the air conditioning unit coil. Employee #1 was electrocuted. The electrical power to the air conditioning unit had not been deenergized and locked or tagged out.
Keywords: head, ventilation, electrocuted, welder, lockout, duct, grating, installing, roof
Inspection Degree Nature Occupation
1 311815492 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close