Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Case Status: CLOSED

Case Status: CLOSED

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 4 4
Initial Penalty $54,612 $0 $0 $0 $0 $54,612
Current Penalty $38,228 $0 $0 $0 $0 $38,228
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Serious 19100022 A02 07/16/2021 08/11/2021 $9,557 $13,653 $0 I - Informal Settlement
  2. 01002A Serious 19100254 C03 I 07/16/2021 08/11/2021 $9,557 $13,653 $0 I - Informal Settlement
  3. 01002B Serious 19100303 B04 07/16/2021 08/11/2021 $0 $0 $0 I - Informal Settlement
  4. 01002C Serious 19100304 F01 I 07/16/2021 08/11/2021 $0 $0 $0 I - Informal Settlement
  5. 01003A Serious 19100254 D09 I 07/16/2021 08/11/2021 $9,557 $13,653 $0 I - Informal Settlement
  6. 01003B Serious 19100254 D09 III 07/16/2021 08/11/2021 $0 $0 $0 I - Informal Settlement
  7. 01003C Serious 19100303 C03 I 07/16/2021 08/11/2021 $0 $0 $0 I - Informal Settlement
  8. 01003D Serious 19100334 A02 I 07/16/2021 08/11/2021 $0 $0 $0 I - Informal Settlement
  9. 01004A Serious 19100304 G05 07/16/2021 08/11/2021 $9,557 $13,653 $0 I - Informal Settlement
  10. 01004B Serious 19100304 G06 II 07/16/2021 08/11/2021 $0 $0 $0 I - Informal Settlement

Accident Investigation Summary
Summary Nr: 134866.015 Event: 04/14/2021Employee Is Electrocuted, Later Dies
At 8:00 a.m. on April 14, 2021, an employee, a maintenance technician, was prepa ring a Miller, Millermatic 350P MIG portable welder machine to weld the frame of a dust collector. The employee plugged the welder into the 30 amp, 480 volt rec eptacle outlet when an electrical short occurred in a splice on the power cable. The electrical short occurred due to two or more bare and uninsulated conductor s touching one another resulting in the grounding wire to become energized. The electricity traveled from the receptacle through the receptacle grounding conduc tor to the grounding lug terminal of the electrical cabinet. The branch circuit and cabinet did not have a grounding conductor or other grounding connection so the electricity energized the entire metal electrical cabinet. The circuit had 1 50 amp fuses installed so they did not interrupt the current when the electrical short occurred. The employee was standing at the electrical cabinet in an area of the floor that was wet and was electrocuted when he contacted the electrical cabinet. The employee was transported to the hospital and died two days later.
Keywords: electric conductor, electric cord, electrical cabinet, electrical splice, electrocuted, system grounding, welder, welding
Inspection Degree Nature Occupation
1 1525767.015 Fatality Machinery maintenance occupations

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.