Accident Investigation Summary
Summary Nr: 14257828Event: 11/27/1984Burns - Phase To Ground Fault
Three employees and a job foreman were erecting new overhead power lines in an open area adjacent to a main highway. The crew was moving an energized phase conductor around a new pole. One of the employees was positioned next to the pole in an insulated aerial lift. A strap jack was attached to a conductor grip holding the energized conductor. An arc was generated between the clevis on the strap jack and a guy. The energized conductor was on a 7200-volt, three-phase system, with a McGraw Edison three-phase-type release with electronic control. The protective device operated to deenergize the line. However, the employee in the aerial lift bucket was fatally injured when he was caught in the arc between the phase line and the guy. He received numerous burns on his body, including burns on his neck, chest, abdomen, back, groin, and left arm, where a hole was burned through his glove.
Keywords: burn, clothing, electric arc, electrical, e ptd, ground fault, guy, elec utility work, winch
Inspection Degree Nature Occupation
1 15001027 Fatality Electric Shock Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.