Inspection Detail
Case Status: CLOSED |
Inspection Information - Office: Virginia Safety 2 | ||||
---|---|---|---|---|
Nr: 1441183.015 | Report ID: 0355112 | Open Date: 10/29/2019 | ||
Classic Air Care Llc | ||||
1022 Beach View Street Norfolk, VA 23503 | Union Status: NonUnion | |||
SIC: | ||||
NAICS: 238220/ Plumbing, Heating, and Air-Conditioning Contractors | ||||
Mailing: 2680 Production Road, Virginia Beach, VA 23454 | ||||
Inspection Type: | Fat/Cat | |||
Scope: | Partial | Advanced Notice: | N | |
Ownership: | Private | |||
Safety/Health: | Safety | Close Conference: | 10/29/2019 | |
Emphasis: | S:Fri | Close Case: | 06/03/2020 | |
Related Activity: | Type | ID | Safety | Health |
Accident | 1513369 |
Case Status: CLOSED |
Violation Summary | ||||||
---|---|---|---|---|---|---|
Serious | Willful | Repeat | Other | Unclass | Total | |
Initial Violations | 5 | 1 | 6 | |||
Current Violations | 3 | 3 | 6 | |||
Initial Penalty | $66,411 | $0 | $0 | $0 | $0 | $66,411 |
Current Penalty | $13,991 | $0 | $0 | $5,515 | $0 | $19,506 |
FTA Amount | $0 | $0 | $0 | $0 | $0 | $0 |
Violation Items | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
# | ID | Type | Standard | Issuance | Abate | Curr$ | Init$ | Fta$ | Contest | LastEvent | |
1. | 01001A | Serious | 19261053 B13 | 04/22/2020 | $2,758 | $5,515 | $0 | I - Informal Settlement | |||
2. | 01001B | Serious | 19261053 B01 | 04/22/2020 | $0 | $0 | $0 | I - Informal Settlement | |||
3. | 01002 | Serious | 19261203 A | 04/22/2020 | 06/09/2020 | $2,100 | $4,200 | $0 | I - Informal Settlement | ||
4. | 01003 | Other | 19260350 H | 04/22/2020 | 05/07/2020 | $2,758 | $5,515 | $0 | I - Informal Settlement | ||
5. | 01005A | Serious | 19260416 A01 | 04/22/2020 | 05/27/2020 | $9,133 | $13,047 | $0 | I - Informal Settlement | ||
6. | 01005B | Serious | 19260417 B | 04/22/2020 | 05/27/2020 | $0 | $13,047 | $0 | I - Informal Settlement | ||
7. | 01005C | Serious | 19260095 A | 04/22/2020 | 05/27/2020 | $0 | $13,047 | $0 | I - Informal Settlement | ||
8. | 01005D | Serious | 19260021 B02 | 04/22/2020 | 05/27/2020 | $0 | $6,525 | $0 | I - Informal Settlement | ||
9. | 01008A | Other | 19101200 E01 | 04/22/2020 | 05/27/2020 | $2,758 | $5,515 | $0 | I - Informal Settlement | ||
10. | 01008B | Other | 19101200 G01 | 04/22/2020 | 05/27/2020 | $0 | $0 | $0 | I - Informal Settlement | ||
11. | 01008C | Other | 19101200 H01 | 04/22/2020 | 06/09/2020 | $0 | $0 | $0 | I - Informal Settlement | ||
12. | 02001 | Other | 19100132 D02 | 04/22/2020 | 06/09/2020 | $0 | $0 | $0 | I - Informal Settlement |
Accident Investigation Summary | ||||||
Summary Nr: 121191.015 | Event: 10/29/2019 | Employee Is Killed By Electrocution While Installing Air Han | ||||
At 2:30 p.m. on October 29, 2019, an employee was stripping wire insulation, using Klein Wire Strippers, to strip a 120v wire to prepare a connection to the terminals in an air handler unit. A 240v electrical circuit had not be deenergized. The employee's thumb touched the energized metal jaws of the wire stripper that were in contact with the 120v conductor and was killed by electrocution. | ||||||
Keywords: thumb, electrocuted, installing, hand tool, electrical work, energized, hvac, connecting | ||||||
Inspection | Degree | Nature | Occupation | |||
---|---|---|---|---|---|---|
1 | 1441183.015 | Fatality | Electric Shock | Heating, air conditioning, and refrig. mechanics |