Inspection Detail
Case Status: VIOLATIONS UNDER CONTEST |
Note: The following inspection has not been indicated as closed. Please be aware that the information shown may change, e.g. violations may be added or deleted. For open cases, in which a citation has been issued, the citation information may not be available for 5 days following receipt by the employer for Federal inspections or for 30 days following receipt by the employer for State inspections.
Inspection Information - Office: Charleston | ||||
---|---|---|---|---|
Nr: 1364871.015 | Report ID: 0316400 | Open Date: 12/04/2018 | ||
Empower Battery, Llc | ||||
221 Butler Ave Bldg 511 Martinsburg, WV 25405 | Union Status: NonUnion | |||
SIC: | ||||
NAICS: 238210/Electrical Contractors | ||||
Mailing: 3100 Walnut Ave, Grants Pass, OR 97527 | ||||
Inspection Type: | Fat/Cat | |||
Scope: | Partial | Advanced Notice: | N | |
Ownership: | Private | |||
Safety/Health: | Safety | Close Conference: | 12/06/2018 | |
Close Case: | ||||
Related Activity: | Type | ID | Safety | Health |
Accident | 1406506 |
Case Status: VIOLATIONS UNDER CONTEST |
Violation Summary | ||||||
---|---|---|---|---|---|---|
Serious | Willful | Repeat | Other | Unclass | Total | |
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $13,260 | $0 | $0 | $0 | $0 | $13,260 |
Current Penalty | $13,260 | $0 | $0 | $0 | $0 | $13,260 |
FTA Amount | $0 | $0 | $0 | $0 | $0 | $0 |
Violation Items | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
# | ID | Type | Standard | Issuance | Abate | Curr$ | Init$ | Fta$ | Contest | LastEvent | |
1. | 01001A | Serious | 19100333 A02 | 05/20/2019 | 05/31/2019 | $13,260 | $13,260 | $0 | 07/11/2019 | - | |
2. | 01001B | Serious | 19100333 C02 | 05/20/2019 | 07/08/2019 | $0 | $0 | $0 | 07/11/2019 | - | |
3. | 01001C | Serious | 19100335 A01 I | 05/20/2019 | 05/31/2019 | $0 | $0 | $0 | 07/11/2019 | - |
Accident Investigation Summary | ||||||
Summary Nr: 111668.015 | Event: 12/04/2018 | Employee Contacts Dc Batteries And Is Electrocuted | ||||
At 11:37 a.m. on December 4, 2018, an employee was replacing 640 batteries in the facilities uninterrupted power supply (UPS) room. The batteries were linked in 16 strings with each string having 40 batteries tied in series. Each string was 540V and 2280 amps. The employee reached overtop of a metal batter rack to retrieve a Styrofoam spacer and his abdomen came in contact with the string of batteries below. The employee was electrocuted. | ||||||
Keywords: battery, electrocuted | ||||||
Inspection | Degree | Nature | Occupation | |||
---|---|---|---|---|---|---|
1 | 1364871.015 | Fatality | Electric Shock | Electrical and electronic technicians |