Case Status: CLOSED
Inspection: 1207005.015 - Casillas Petroleum Corp.

Inspection Information - Office: Wichita

Nr: 1207005.015Report ID: 0729700Open Date: 02/01/2017

Casillas Petroleum Corp.
Sec 5, Twp 27s, R34wnull
Satanta, KS 67870
Union Status: NonUnion
SIC:
NAICS: 213112/Support Activities for Oil and Gas Operations
Mailing: 348 Rd. Ddnull, Satanta, KS 67870

Inspection Type:Referral
Scope:Partial Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:02/01/2017
Emphasis: L:Oilgas, L:RepvehicleClose Case:04/06/2017

Related Activity:TypeIDSafetyHealth
 Referral1178145 Yes  
Case Status: CLOSED

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $9,696 $0 $0 $0 $0 $9,696
Current Penalty $4,848 $0 $0 $0 $0 $4,848
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Serious 19100303 F02 03/21/2017 04/14/2017 $3,232 $6,464 $0 I - Informal Settlement
  2. 01002 Serious 19100333 B02 I 03/21/2017 04/21/2017 $1,616 $3,232 $0 I - Informal Settlement

Accident Investigation Summary
Summary Nr: 92715.015Event: 01/30/2017Employee Is Burned While Working On Electrical Equipment
At 12:30 p.m. on January 30, 2017, an employee was repairing the head switch of the primary motor control center at an oil pumping site. The oil pump motor cont rol center and the saltwater motor control center were not labeled as to what ci rcuits were either controlled by them and/or passed through them. The motor cont rol center was secured in anticipation of replacing the head switch. The employe e opened a nearby junction box to perform the initial disconnection of wiring to the switch. The employee came into contact with a 480 volt unused circuit that passed through the motor control center. This 480 volt circuit was not de-energi zed by the cutout used to secure the motor control center and the employee did n ot test the circuits within the junction box to ensure they were all de-energize d and sustained extensive electrical burns to the right hand and less serious bu rns to the left.
Keywords: burn, electrical, hand, lockout, protective clothing, test equipment
Inspection Degree Nature Occupation
1 1207005.015 Hospitalized injury Occupation Not Listed

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.