Inspection Detail
Inspection: 119748085 - Imperial Hotels Inc., Dba Econo Lodge
|
Inspection Information - Office: Ca Foster City District Office | ||||
Nr: 119748085 | Report ID: 0950613 | Open Date: 02/08/1994 | ||
Imperial Hotels Inc., Dba Econo Lodge | ||||
222 South Airport Blvd South San Francisco, CA 94080 | Union Status: NonUnion | |||
SIC: 7011/Hotels and Motels | ||||
Mailing: 2361 Rosecrans Ave. (Suite 375), El Segundo, CA 90245 | ||||
Inspection Type: | Accident | |||
Scope: | Partial | Advanced Notice: | N | |
Ownership: | Private | |||
Safety/Health: | Safety | Close Conference: | 03/24/1994 | |
Close Case: | 05/11/2007 | |||
Related Activity: | Type | ID | Safety | Health |
Accident | 361345374 |
Serious | Willful | Repeat | Other | Unclass | Total | |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $275 | $0 | $0 | $0 | $0 | $275 |
Current Penalty | $275 | $0 | $0 | $0 | $0 | $275 |
FTA Amount | $0 | $0 | $0 | $0 | $0 | $0 |
# | ID | Type | Standard | Issuance | Abate | Curr$ | Init$ | Fta$ | Contest | LastEvent | |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 763 D01 | 03/25/1994 | 02/08/1994 | $25 | $25 | $0 | - | ||
2. | 02001 | Serious | 3328 G | 03/25/1994 | 02/08/1994 | $250 | $250 | $0 | - |
Accident Investigation Summary | ||||||
---|---|---|---|---|---|---|
Summary Nr: 170209860 | Event: 02/03/1994 | Employee Slightly Injured In Boiler Explosion | ||||
At approximately 11:00 a.m. on February 3, 1994, Employee #1, an Econo Lodge employee, was working in a room in which the motel's main water heater boiler was located when, without warning, the heater exploded. The explosion blew a hole in the adjacent wall, and fragments of the boiler injured Employee #1, but not seriously and not requiring hospitalization. When the water heater's pressure relief valve was removed and inspected, it was found to be clogged by what appeared to be heavy rust deposits, and therefore not in operating condition. The heater was also lacking a water level switch. | ||||||
Keywords: boiler, clogged, explosion, valve, water heater, hotel | ||||||
Inspection | Degree | Nature | Occupation | |||
1 | 119748085 | Non Hospitalized injury | Cut/Laceration | Occupation not reported |