Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 102963337 - Gavdette Electric, Inc.

Inspection Information - Office: Tampa

Nr: 102963337Report ID: 0420600Open Date: 07/20/1988

Gavdette Electric, Inc.
659 Southeast U.S. Highway 19
Crystal River, FL 32629
Union Status: NonUnion
SIC: 1731/Electrical Work
Mailing: P.O. Box 2820, Homosassa Springs, FL 32647

Inspection Type:Accident
Scope:Complete Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:07/20/1988
Planning Guide: Safety-Construction Close Case:12/15/1988

Related Activity:TypeIDSafetyHealth
 Accident360453179    

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 3 1 4
Current Violations 3 1 4
Initial Penalty $780 $0 $0 $0 $0 $780
Current Penalty $780 $0 $0 $0 $0 $780
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Serious 19260021 B02 12/02/1988 12/21/1988 $300 $300 $0 -
  2. 01002 Serious 19260404 B01 II 12/02/1988 12/05/1988 $240 $240 $0 -
  3. 01003 Serious 19260451 E04 12/02/1988 12/06/1988 $240 $240 $0 -
  4. 02001 Other 19260451 E09 12/02/1988 12/06/1988 $0 $0 $0 -

Accident Investigation Summary
Summary Nr: 601740Event: 07/18/1988Electric Shock - Contact With Live Parts Thru Metal Tape
AN ELECTRICIAN'S HELPER WAS PULLING NEW CONDUCTORS THROUGH AN EXISTING CONDUIT IN A STORE THAT WAS BEING REMODELED. HE WAS WORKING FROM A MOBILE SCAFFOLD, ON A LEVEL WITH THE DROP CEILING, USING A METAL PULLING TAPE TO PULL THE NEW CONDUCTORS. TWO EXTENSION CORD SETS, WHICH WERE PLUGGED TOGETHER, WERE LYING IN AN AREA NORTH OF WHERE THE EMPLOYEE WAS WORKING. AS THE METAL TAPE WAS PULLED THROUGH THE CONDUIT, IT WAS ALSO BEING PUSHED INTO THE AREA WHERE THE EXTENSION CORD SETS WERE LYING. THE METAL TAPE APPARENTLY CONTACTED THE ENERGIZED BLADES OF ONE OF THE EXTENSION CORDS WHERE THE TWO CORDS WERE PLUGGED TOGETHER, ELECTROCUTING THE EMPLOYEE. THERE WERE NO OTHER ENERGIZED CIRCUIT PARTS IN THE AREA, EXCEPT FOR A FLUORESCENT LIGHTING FIXTURE. THE FIXTURE WAS CHECKED AND FOUND TO BE GROUNDED AND TO BE ABSENT OF CURRENT LEAKAGE. THE CONDUCTORS THAT WERE BEING PULLED WERE NOT CONNECTED TO A SOURCE OF POWER (THEY WERE BEING FED FROM SPOOLS). THE EMPLOYEE HAD ONLY BEEN WORKING FOR THE COMPANY FOR ABOUT 2 WEEKS AND HAD NOT RECEIVED ANY SAFETY TRAINING.
Keywords: metal wire, electrical, e c, cord connector, electrician, electrocuted
Inspection Degree Nature Occupation
1 102963337 Fatality Electric Shock Electricians' apprentices

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.