Accident: 762609 - Electric Shock - Ground Fault In Electrical Service

Accident: 762609 -- Report ID: 0454712 -- Event Date: 08/19/1988
InspectionOpen DateSICEstablishment Name
10557006308/24/19881731Wayne'S Plumbing & Electrical Services Company
AN EMPLOYEE WAS MAKING FINAL ADJUSTMENTS TO A RESIDENTIAL WIRING SYSTEM. TWO SECTIONS OF 12/2 AWG NON-METALLIC-SHEATHED CABLE (ROMEX) WERE USED TO SUPPLY POWER FROM THE TEMPORARY ELECTRICAL SERVICE TO THE METER BASE FOR THE RESIDENCE. THIS ALLOWED THE WIRING INSIDE THE HOUSE TO BE INSPECTED AND EQUIPMENT TO BE CHECKED TO ENSURE THAT IT WORKED PROPERLY. THE EMPLOYEE WAS UNDER THE HOUSE CONNECTING THE GROUNDING ELECTRODE CONDUCTOR TO THE COLD WATER PIPE SERVING AS THE GROUNDING ELECTRODE. THE POLARITY OF THE TEMPORARY SERVICE WAS REVERSED, AND THE GROUNDING ELECTRODE CONDUCTOR WAS ACTUALLY CONNECTED TO AN UNGROUNDED CIRCUIT CONDUCTOR. THE EMPLOYEE WAS ELECTROCUTED AS HE WAS MAKING THE CONNECTION TO THE WATER PIPE.
Keywords: e gi iv, electrical, reverse polarity, electrician, electrocuted, electrical work, lockout, ground fault, system grounding
Employee # Inspection Age Sex Degree Nature Occupation
1 105570063 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close