Accident: 723254 - Electric Shock - Direct Contact With Energized Parts

Accident: 723254 -- Report ID: 0521700 -- Event Date: 09/17/1993
InspectionOpen DateSICEstablishment Name
10871947709/17/19933471Sebright Induction Metal Treating Co.
An employee was performing the final check of a Linberg Hi-Frequency induction generator (Tag. No. 1-175; Contract No. DARE-11-67-C-0289(T)) after the installation of three new capacitors. The three 0.0054-microfarad, water-cooled capacitors (General Electric Model No. 1290; Catalog No. 19F2411) were rated at 9000 volts and 165 amperes, rms. The employee noticed water leaking from one of the hoses that connect to the capacitors. He then opened the door to the unit, which was interlocked to deenergize the generator. However, he did not ground the circuit to discharge the capacitors. When he stepped into the generator, he apparently contacted a circuit part that was still energized through the residual charge on the capacitors and was electrocuted.
Keywords: protective grounding, e gi iv, electrical, electrocuted, capacitor, lockout, elec circ part--misc
Employee # Inspection Age Sex Degree Nature Occupation
1 108719477 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close