Accident: 688960 - Burn - Electrical Fault In Disconnect

Accident: 688960 -- Report ID: 0522300 -- Event Date: 01/30/1996
InspectionOpen DateSICEstablishment Name
12193270101/30/19963462Park Drop Forge
An employee was replacing 60-ampere fuses in a disconnect box on a 480-volt busway. The disconnect was defective, and the circuit was still energized even when the disconnect's cover was opened. Additionally, the 600-ampere circuit breaker protecting this busway was deliberately blocked; thus, the breaker could not trip when an overload occurred.. As the employee, who did not test the circuit before beginning work, was replacing the fuses, an electrical fault occurred. The employee sustained severe burns as a result of the ensuing electric arc. He was hospitalized for his injuries, but died following surgery 2 days after the accident.
Keywords: burn, electric arc, e gi iv, electrical, electrical work, lockout, circuit breaker, electric shock, disconnecting means, electrical fault
Employee # Inspection Age Sex Degree Nature Occupation
1 121932701 Fatality Burn/Scald(Heat) Not specified mechanics and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close